FR200 Series Vector control inverter
- 124 -
This parameter sets communication error detection time. When it's set to 0.0, no communication
Error will be reported.
F15.04
Response
time delay
Range:0
~
200ms
Default:1ms
Set response time delay of this drive to the master.
F15.05
Master-slave Communication
Mode
Range:0
~
1
Default:0
0: The inverter is the slave
PC as master controls the drive. This supports all communication protocols.
1: The inverter is the master
This drive as master sends current running frequency data or set frequency data (F15.06) through
RS-485 port to 2001H. Data cannot be received but sent.
F15.06
The Master Communication
Sending Data
Range:0
~
1
Default:0
0: Set frequency
1: Current running frequency
F15.07
Informaion
return
when
communication error
Range
:
0
~
1
Default
:
1
0: No return
1: Return
F15.08
Group
U00.00
output
frequency numerical attribute
Range
:
0
~
1
Default
:
0
0:Positive and negative value
(
Forward: Positive value
,
reverse: negative value
)
1: Absolute value
Group F16 Keys and Display of Keypad Parameters
F16.00
MF.K key setting
Range:0
~
2
Default:1
0: No function
1: Jog
2: Forward/reverse switchover
3: Run command sources shifted
F16.01
Function of STOP/RST key
Range:0
~
1
Default:1
0: STOP/RST key valid only when under keypad control
1: STOP/RST key valid under any run command source
F16.02
Keys locked option
Range:0
~
4
Default:0
0: Not locked
1: Full locked
2: Keys locked other than RUN, STOP/RST
3: Keys locked other than STOP/RST
4: Keys locked other than >>
F16.03
LED displayed parameters
setting 1 on running status
Range:0
~
99
Default:0
F16.04
LED displayed parameters
setting 2 on running status
Range:0
~
99
Default:6
F16.05
LED displayed parameters
setting 3 on running status
Range:0
~
99
Default:3
F16.06
LED displayed parameters
setting 4 on running status
Range:0
~
99
Default:2
Sets LED displayed parameters on running status. When a number of parameters are selected to
be displayed, skim- through could be performed using key >> on keypad. 0
~
99 corresponding
U00.00
~
U00.99.
F16.07
LED displayed parameters
setting 1 on stop status
Range:0
~
99
Default:1
F16.08
LED displayed parameters
setting 2 on stop status
Range:0
~
99
Default:6
F16.09
LED displayed parameters
setting 3 on stop status
Range:0
~
99
Default:15
F16.10
LED displayed parameters
Range:0
~
99
Default:16