  CHECK THAT : 

  the motor rating is compatible with the drive rating 

  the motor winding connection is compatible with the drive output voltage  

   (refer to chapter 5

;

 section 1.3.) 

  AC input power circuit breaker of the correct rating is installed upstream on the low 

voltage 
    switch-board  (refer to chapter 5, section 1.2.) 

  the drive is firmly attached in an upright position and is properly ventilated 

 

7.1. Procedure I

 

 -

  remote (external) control without using TELECONTROL - remote control unit 

  connect the control cable to terminal board (shown in FIG 2) 

  put  the AC input power circuit breaker in "ON" position - the red "POWER" light goes on. 

  In the event of a fault

;

 the red "FAILURE" light goes on. 

 

7.1.1.

 

Speed control

 

         

Three binary preset speed inputs (control terminals 

F1

;

 

F2

;

 

F3

) select 8 preset speeds. 

                    

 

change-over 

switch 

position 

(telecontrol) 

F1  F2  F3

 
 
 
 
 
 
 
 

output frequency 

0 0 0

20 

Hz 

0 0 1

25 

Hz 

0 1 0

30 

Hz 

0 1 1

35 

Hz 

1 0 0

40 

Hz 

1 0 1

44 

Hz 

1 1 0

47 

Hz 

1 1 1

50 

Hz 

 

 

NOTE :  0 = external contact open (disconnecting 24V DC from the terminal) 

          

  

1 = external contact closed (connecting 24V DC to the terminal) 

 

 

Acceleration/deceleration between preset values : 5 Hz/s 

 

7.1.2.

 

"Run/stop" 

  connect 24V DC to the terminal 

1

 (control switch or PLC output) : 

     The motor will start and run up to the set speed. 

  disconnect 24V DC from the terminal 

1

 :  

 

 

The motor will coast to a stop. 

 

7.2. Procedure II -

 remote (external) control, using TELECONTROL - remote control unit    

 

  connect the control cable to the terminal boards at the drive and the TELECONTROL  

    (shown in FIG 4) 

  put the AC input power circuit breaker in "ON" position - the red "POWER" light goes on. 

  In the event of a fault

;

 the red "FAILURE" light goes on. 

 

 
 
 
 
 
 
 
 
 

                                                                                                                                           FIG 4 

                                               
                                                              

 
 

FIG 3 

1

2

3

4

5

6

1

2

3

4

5

9

6

7

F

R

E

C

O

N

  

F

ID

-L

T

E

L

E

C

O

N

T

R

O

L

 F

ID

2

 /

  

A

L

T

-P

2

7

8

Содержание FID-L110

Страница 1: ...Praha 4 CZECH REPUBLIC tel 420 241 71 32 44 45 fax 420 241 72 10 52 E mail info frecon cz http www frecon cz FRECON FID L18 37 55 75 110 150 220 250 SPEED DRIVES FOR STANDARD AC INDUCTION MOTORS 0 18k...

Страница 2: ...leration deceleration between preset values 5Hz s Apparent power kVA 0 6 1 0 1 4 1 6 2 2 2 8 4 0 4 5 Overload 150 30 sec Nominal current A 1 4 2 4 3 0 4 0 5 5 7 0 10 0 11 3 Modulation PWM 18kHz V f ch...

Страница 3: ...control power supply wiring and in certain internal parts of the drive are capable of causing severe electric shock and may be lethal WARNING Whenever the drive has been energised it must be isolated...

Страница 4: ...rth terminal and the drive earth terminal Installations with long cable runs to the motor i e above approx 30 m may need the addition of motor line chokes to prevent nuisance tripping of the drive cau...

Страница 5: ...ches or PLC outputs Three binary preset speed inputs select 8 preset speeds Input voltage min 15 VDC Input current cca 8 5 mA 24 VDC nominal 24 VDC max 30 VDC Input signal delay max 5 ms Logic output...

Страница 6: ...set speeds change over switch position telecontrol F1 F2 F3 output frequency 1 0 0 0 20 Hz 2 0 0 1 25 Hz 3 0 1 0 30 Hz 4 0 1 1 35 Hz 5 1 0 0 40 Hz 6 1 0 1 44 Hz 7 1 1 0 47 Hz 8 1 1 1 50 Hz NOTE 0 exte...

Страница 7: ...0 x 80 x 55 mm h x w x d mounting externally anywhere convenient at a distance permitted by a maximum cable length of 50 m from the drive to the TELECONTROL 9 2 EXTERNAL RFI FILTER To conform to EMC s...

Страница 8: ...bles are altered in any way the filter will operate but compliance with any emission standard is no longer assured Input cable into the filter filtered cable and no control circuit should be run paral...

Страница 9: ...be isolated before work may continue A period of five minutes must elapse after isolation to allow the internal capacitors to discharge fully Until the discharge period has passed dangerous voltages...

Отзывы: