The layout of the power terminals and connections is shown in FIG 1. 
 

 

FIG 1 

 

              

 

 
 
 
 

 

 

 

 
 
 
 

5.1.2.

  

Recommended protection devices installed upstream of the drive and cabling 

 
 

Drive model 

FID-L 

18 

37 

55 

75 

110 

150 

220 

250 

       fuse ratings* 

6A 

10A 

16A 

20A  25A

cable size (for 3-core)**       mm

2

 1,5 2,5 

    *  

The use slow protection devices (curve C) is recommended, because a current surge may appear at power on. 

                  ** Cable sizes are recommendations only. Cabling should  conform to local codes of practice and regulations.  

 

5.1.3. Motor connection 

  No protection devices between the drive and the motor are recommended. The power connections 

from  the drive output to the motor may be switched, for isolation purposes

;

 but not for control 

purposes. 

 

  Connection between the drive and the motor as short as possible are recommended to prevent 

emissions from the motor cable. 

  If it is not possible, screened or armoured cable may be used . The screen or armour should be 

connected in the same way as for standard cable (to both the motor earth terminal and the drive 
earth terminal). 

 

  Installations with long cable runs to the motor (i.e. above approx. 30 m), may need the addition of 

motor line chokes to prevent nuisance tripping of the drive caused by capacitative  leakage 
effects. 

 

 

Output voltage of the drive FRECON FID - L : 3 x 230 V ! 

 

MOTOR WINDING CONNECTION MUST BE COMPATIBLE WITH THIS VOLTAGE ! 

IN THE MOST CASES : DELTA CONNECTION 

 

 

5.2.  Motor speed 

  Standard squirrel-cage ac induction motors are designed as single speed machines. If it is 

intended to use the capability of the drive to run the motor at speeds above its designed 
maximum, it is strongly recommended that the motor  manufacturer is consulted first. 

 

  The principal risks due to overspeeding are the destruction of the rotor by centrifugal force, or of 

the bearings by vibration or heat.  

 

  Low speed is liable to result in overheating of the motor because the effectiveness of the internal 

cooling fan reduces in proportion to the square of the reduction of speed. Motors should be 
equipped with thermistor protection, and if full benefit of the use of  low speeds is to be gained 
from a variable speed drive it may be necessary to arrange additional cooling for the motor. 

 

Содержание FID-L110

Страница 1: ...Praha 4 CZECH REPUBLIC tel 420 241 71 32 44 45 fax 420 241 72 10 52 E mail info frecon cz http www frecon cz FRECON FID L18 37 55 75 110 150 220 250 SPEED DRIVES FOR STANDARD AC INDUCTION MOTORS 0 18k...

Страница 2: ...leration deceleration between preset values 5Hz s Apparent power kVA 0 6 1 0 1 4 1 6 2 2 2 8 4 0 4 5 Overload 150 30 sec Nominal current A 1 4 2 4 3 0 4 0 5 5 7 0 10 0 11 3 Modulation PWM 18kHz V f ch...

Страница 3: ...control power supply wiring and in certain internal parts of the drive are capable of causing severe electric shock and may be lethal WARNING Whenever the drive has been energised it must be isolated...

Страница 4: ...rth terminal and the drive earth terminal Installations with long cable runs to the motor i e above approx 30 m may need the addition of motor line chokes to prevent nuisance tripping of the drive cau...

Страница 5: ...ches or PLC outputs Three binary preset speed inputs select 8 preset speeds Input voltage min 15 VDC Input current cca 8 5 mA 24 VDC nominal 24 VDC max 30 VDC Input signal delay max 5 ms Logic output...

Страница 6: ...set speeds change over switch position telecontrol F1 F2 F3 output frequency 1 0 0 0 20 Hz 2 0 0 1 25 Hz 3 0 1 0 30 Hz 4 0 1 1 35 Hz 5 1 0 0 40 Hz 6 1 0 1 44 Hz 7 1 1 0 47 Hz 8 1 1 1 50 Hz NOTE 0 exte...

Страница 7: ...0 x 80 x 55 mm h x w x d mounting externally anywhere convenient at a distance permitted by a maximum cable length of 50 m from the drive to the TELECONTROL 9 2 EXTERNAL RFI FILTER To conform to EMC s...

Страница 8: ...bles are altered in any way the filter will operate but compliance with any emission standard is no longer assured Input cable into the filter filtered cable and no control circuit should be run paral...

Страница 9: ...be isolated before work may continue A period of five minutes must elapse after isolation to allow the internal capacitors to discharge fully Until the discharge period has passed dangerous voltages...