background image

 
 

7

7.2.1. Speed control 

 potentiometer 

 

7.2.2. "Run/stop" 

 change-over 

switch 

 

function (refer to chapter 7

;

 section 1.2.) 

 

7.2.3. "Forward/reverse" 

  change - over switch 

 

function (refer to chapter 7

;

 section 1.3.) 

 

7.2.4. Drive status indication 

  LED " FAILURE " (red) : internal or external trip

;

 the drive is stopped (disconnected from the load) 

 

7.3. Procedure III 

- local control, using MINITERMINAL (control pod)  

  remove the connector cover on the front panel of the drive 

  connect the control cable from the control pod to the connector on the front panel of the drive 

  put the AC input power circuit breaker in "ON" position - the red "POWER" light goes on. 

 

In the event of a fault

;

 the red "FAILURE" light goes on. 

  press the CONTROL MODE SELECTION key (LOC/REM) on the control pod - select local (keypad) 

control.  

 

The red "LOC" light on the control pod goes on. 

  all operational functions of the drive and motor can be controlled and all parameter values can be 

changed from the keypad (refer to user manual for the MINITERMINAL) 

 

8. Reset of the drive after a trip signal 

 

Two modes are available : 

  short time disconnecting of the drive from the supply and reconnecting 

  STOP signal activation  

     Reset mode is set by parameter "CRTR" (refer to user manual for the MINITERMINAL) 

 

 

 

NOTE :

 restart of the drive ("START" signal activation) is recommended when the motor is stopped ! 

 
 

9. Options 

9.1. FRECON MINITERMINAL  (control pod) 

       Combines keypad and display functions :  

  local /remote control selection 

  local control (run/stop, forward/reverse, output freq. control 

     resolution : 0,01 Hz) 

  drive parameter values adjustment and display (LCD screen) 

  user sets programming possibility (i.e. storing all functional 

     parameters into EEPROM for automatic or manual restore) 

  required and actual output frequency monitoring (LCD screen) 

  operational status LED indication : run, fwd, rev, local (keypad)  

     control  

  fault codes display 

  MOUNTING : externally anywhere convenient at a distance  

     permitted by a maximum cable length of 6 m from the drive to the pod. 

 
 
 
 
 
 
 
 
 
 

Содержание FIA-L110

Страница 1: ...CZECH REPUBLIC tel 420 241 71 32 44 45 fax 420 241 72 10 52 E mail info frecon cz http www frecon cz FRECON FIA L18 37 55 75 110 150 220 250 PROGRAMMABLE SPEED DRIVES FOR STANDARD AC INDUCTION MOTORS...

Страница 2: ...before work may continue A period of five minutes must elapse after isolation to allow the internal capacitors to discharge fully Until the discharge period has passed dangerous voltages may be presen...

Страница 3: ...W up to 500Hz Apparent power kVA 0 6 1 0 1 4 1 6 2 2 2 8 4 0 4 5 Overload 150 30 sec Nominal current A 1 4 2 4 3 0 4 0 5 5 7 0 10 0 11 3 Modulation PWM 18kHz V f characteristic adjustable Control logi...

Страница 4: ...control power supply wiring and in certain internal parts of the drive are capable of causing severe electric shock and may be lethal WARNING Whenever the drive has been energised it must be isolated...

Страница 5: ...andard cable to both the motor earth terminal and the drive earth terminal Installations with long cable runs to the motor i e above approx 30 m may need the addition of motor line chokes to prevent n...

Страница 6: ...eter 2 20 k recommended value 10 k Logic inputs run stop control switch or PLC output forward reverse control switch or PLC output Input voltage min 15 VDC Input current approx 8 5 mA 24 VDC nominal 2...

Страница 7: ...is set by parameter ACC refer to chapter 9 section 1 disconnect 24 V DC from the terminal 3 The motor will ramp or coast to a stop Deceleration is set by parameter DEC stopping mode is set by paramete...

Страница 8: ...led and all parameter values can be changed from the keypad refer to user manual for the MINITERMINAL 8 Reset of the drive after a trip signal Two modes are available short time disconnecting of the d...

Страница 9: ...age FOUT 6 8 FBAS U7 32 93 VMAX output voltage FOUT 7 8 FBAS CINP 0 1 2 3 reference input selection CSTP 0 1 stopping mode selection CRTR 0 1 reset mode selection SET support parameter for user set pr...

Страница 10: ...the filter follow the instructions in FIG 4 FIG 4 The filter cubicle is necessary to install near of the drive NOTE Connections must be made with the short length of screened cables If these cables ar...

Отзывы: