background image

 
 

4

The layout of the power terminals and connections is shown in FIG 1. 

L N

U V W

-B +B

3~

M

PE

1p

h

a

se

 2

3

0

V

/5

0

H

z

Braking unit

(option)

N

 

                                   FIG 1 

 

5.1.2. Recommended protection devices installed upstream of the drive and cabling 

Drive model 

FIA-L 

18 

37 

55 

75 

110 

150 

220 

250 

     fuse ratings* 

6A 

10A 

16A 

20A  25A

     cable size (for 3-core)**  mm

2

 1,5 

2,5 

4,0 

      * 

The use of slow protection devices (curve C) is recommended because a current surge may appear at power on. 

                  **

Cable sizes are recommendations only. Cabling should conform to local codes of practice and

 

regulations.  

 

5.1.3. Motor connection 

  No protection devices between the drive and the motor are recommended. The power connections 

from  the drive output to the motor may be switched, for isolation purposes

;

 but not for control 

purposes. 

  Connection between the drive and the motor as short as possible are recommended to prevent 

emissions from the motor cable. 

  If it is not possible, screened or armoured cable may be used . The screen or armour should be 

connected in the same way as for standard cable (to both the motor earth terminal and the drive 
earth terminal). 

  Installations with long cable runs to the motor (i.e. above approx. 30 m), may need the addition of 

motor line chokes to prevent nuisance tripping of the drive caused by capacitative  leakage effects. 

 

 

Output voltage of the drive FRECON FIA - L : 3 x 230 V ! 

 

MOTOR WINDING CONNECTION MUST BE COMPATIBLE WITH THIS VOLTAGE ! 

IN THE MOST CASES : DELTA CONNECTION 

 

 

5.2. Motor speed 

   Standard squirrel-cage ac induction motors are designed as single speed machines. If it is intended 

to use the capability of the drive to run the motor at speeds above its designed maximum, it is 
strongly recommended that the motor  manufacturer is consulted first. 

   The principal risks due to overspeeding are the destruction of the rotor by centrifugal force, or of the 

bearings by vibration or heat.  

   Low speed is liable to result in overheating of the motor because the effectiveness of the internal 

cooling fan reduces in proportion to the square of the reduction of speed. Motors should be 
equipped with thermistor protection, and if full benefit of the use of low speeds is to be gained from 
a variable speed drive it may be necessary to arrange additional cooling for the motor. 

 

 

Содержание FIA-L110

Страница 1: ...CZECH REPUBLIC tel 420 241 71 32 44 45 fax 420 241 72 10 52 E mail info frecon cz http www frecon cz FRECON FIA L18 37 55 75 110 150 220 250 PROGRAMMABLE SPEED DRIVES FOR STANDARD AC INDUCTION MOTORS...

Страница 2: ...before work may continue A period of five minutes must elapse after isolation to allow the internal capacitors to discharge fully Until the discharge period has passed dangerous voltages may be presen...

Страница 3: ...W up to 500Hz Apparent power kVA 0 6 1 0 1 4 1 6 2 2 2 8 4 0 4 5 Overload 150 30 sec Nominal current A 1 4 2 4 3 0 4 0 5 5 7 0 10 0 11 3 Modulation PWM 18kHz V f characteristic adjustable Control logi...

Страница 4: ...control power supply wiring and in certain internal parts of the drive are capable of causing severe electric shock and may be lethal WARNING Whenever the drive has been energised it must be isolated...

Страница 5: ...andard cable to both the motor earth terminal and the drive earth terminal Installations with long cable runs to the motor i e above approx 30 m may need the addition of motor line chokes to prevent n...

Страница 6: ...eter 2 20 k recommended value 10 k Logic inputs run stop control switch or PLC output forward reverse control switch or PLC output Input voltage min 15 VDC Input current approx 8 5 mA 24 VDC nominal 2...

Страница 7: ...is set by parameter ACC refer to chapter 9 section 1 disconnect 24 V DC from the terminal 3 The motor will ramp or coast to a stop Deceleration is set by parameter DEC stopping mode is set by paramete...

Страница 8: ...led and all parameter values can be changed from the keypad refer to user manual for the MINITERMINAL 8 Reset of the drive after a trip signal Two modes are available short time disconnecting of the d...

Страница 9: ...age FOUT 6 8 FBAS U7 32 93 VMAX output voltage FOUT 7 8 FBAS CINP 0 1 2 3 reference input selection CSTP 0 1 stopping mode selection CRTR 0 1 reset mode selection SET support parameter for user set pr...

Страница 10: ...the filter follow the instructions in FIG 4 FIG 4 The filter cubicle is necessary to install near of the drive NOTE Connections must be made with the short length of screened cables If these cables ar...

Отзывы: