22
Procedure
To test:
After testing is completed:
IMPORTANT
: When the procedure is complete, you
MUST
remove the needle valve.
1. The needle valve kit (TS-ALNIP) and 3.0 GPH (11.4 L/h) Leak Generator (TS-ALCAL) should be
installed in the STP manifold. The line must be purged of all air prior to learning the line.
2. Open the needle valve with the leak generator in an approved container to catch any
product. Let the line pressure bleed down to 0. Make sure that the pressure reads 0 on the
pressure gauge installed on the needle valve kit.
3. Navigate to the line control screen on either the touch screen or by the web page. Locate
the learn section and press start.
4. If the learn process is performed correctly the screen will show the events in the following
sequence,
• Learning zero offset
• The system turns on the STP to learn pump pressure
• Learn the pressure decay curve
5. When finished, the message Learn Completed – No Errors is displayed on-screen and the
Not Learned indicator will become inactive.