Fuel Management Systems (FMS) Line Application Set-Up
Setting up the lines establishes which transducer and relay is used on the specific line and allows
the user to change certain parameters in the operation of the line leak testing. Make sure the
line is holding at or above the minimum required pressure. If the pressure is too low, review the
check-valve used, and adjust the pump/pump controller for proper pressure.
Parameter
Parameter Value
Number of lines
Number of product lines
Name
Text box, name each channel to easily identify in the mapping.
Submersible Pump Module
Select either power supply module or relay module depending upon which
relay is being used for pump control, or if TPI is being used. If Power Supply
Board is selected and a relay from this power supply board was associated to
a pump, an additional option will show up to indicate if TPI or relay will be used.
TPI
Yes or No
Submersible Pump Channel
Select the channel that the submersible controller is connected to.
Transducer
Select the transducer installed in the line.
Enable SLLD
Select Yes to enable Statistical Line Leak Detection. No disables this feature.
NOTE: When enabled there will be no option for wait times between test in
monthly testing sections of programming.
Product
Enter Product name (grade)
Enable
Select Yes-Enables line testing. No, there is no line testing in operation on this
line.
Pressure Up Test Wait Time *
Default is 4 Seconds. This is the time that the gauge waits for the line to
pressure up above 12 PSI (83 kPa).
Catch Pressure Wait Time *
Default is 2 seconds. This is the time the gauge waits after the pump turns off
to make sure the pressure is at least 12 PSI (83 kPa).
Dispenser Pressure Test
When selected, this gauge monitors the line pressure while dispensing. If the
pressure decreases to 7.5 PSI (52 kPa), the line goes into alarm mode. The
pump shuts off and is disabled.
Catch and Sudden Pressure Test
Enables Catch Pressure test and sudden pressure loss alarms - No disables.
Catch pressure test and sudden pressure loss alarm notification.
Gross / Monthly / Annual Tests
Enable
Select Yes. This allows the TS-LS500 to run the tests.
Wait Period Between Tests
Default setting is 0 days. (This is the scheduling for line test after the test
passed).
Shutdown on Test Fail
If selected, this will shut down the submersible if that line fails that type of test
* These settings typically will not need to be change. If the site is experiencing failed to pressure
up or catch pressure alarms try extending the time to resolve. Some commercial dispensers
require the catch and sudden pressure feature to be disabled.