10
4-20mA Input Module
TS-LSU500 Transducers use a single 4-20mA channel per product line which allows the console to
monitor the pressure on each product line.
Parameter
Parameter Value
Channels
Select the number of channels used for LLD.
Name
Text box, name each channel to easily identify in the mapping.
Service Type
Select Line Leak Detection. This indicates that the type of device connected to the channel to
indicate that the device is a TS-LS500 transducer.
Example: 4-20mA Input Module TS-LS500 Setup
Group Name
Parameter Name
Parameter Value
4-20mA Input Modules
Module 1
Channels 1
Channel 1
Name Unleaded Transducer
Service Type Line Leak Detection
Relay Module
The 2A relay module contains 8 separate relays (relay channels). The 10A relay module contains
6 relay channels. Each relay is used by the console to turn a specific STP on or off in applications
where Turbine Pump Interface (TPI) is not used.
Parameter
Parameter Value
10 Amp
Select either yes or no depending upon which type of relay module is used
Channels
Select the number of channels that will be used
Name
Text box, name each channel to easily identify in the mapping
Enabled
Select Yes
Type
Submersible Pump
Polarity
Normal
Logic
OR logic
Physically Wired As
Normally Open
Number of Inputs*
1 for transducer plus number of AC inputs for this product, plus any other inputs to operate the
submersible pump
Type
Module type that the input is on
Channel
Specific channel the input is wired to.
* Calculate the total number of inputs that need to turn on the STP:
1 transducer
+ Number of AC inputs for the specific line
+ Any other inputs to operate the STP
= Total number of inputs