6
Explosion Proof TS-LS500E
Installation
NOTE:
The Explosion Proof 4-20mA Input Module has a RED face.
WARNING:
Lockout and tag circuit breakers, and disconnect console power wiring before
installing or servicing any system wiring.
WARNING:
DO NOT make transducer wiring connections with power connected to the
console or any module.
CAUTION:
Do not run intrinsically safe (IS) wiring and non-intrinsically safe (non-IS) wiring in
the same conduit.
NOTE:
TS-LS500E must be installed in accordance with the national electrical code, ANSI/NFPA
70, CEC or other applicable national or local codes.
NOTE:
The explosion-proof transducer needs to have explosion-proof conduit to the head of the
transducer.
1. Pull the wiring through the explosion proof conduit that will be used for the TS-LSU500E
transducer.
2. Mount the TS-LSU500E in the pump manifold.
3. The TS-LSU500E wiring must enter the console in Explosion Proof conduit through a knockout
on the Hazardous side of the barrier. Secure each pair of transducer wires to a single channel
on the 4-20mA Input Module. Always start at the first available channel and do not skip
channels. For example, if channels one through three are already being used for another
application channel 4 must be used. Be sure to connect the wires to the correct polarity (+/-).
If the transducer is wired backwards it will not function.