![Franklin Fueling Systems GUARDIAN SPGC-220. Скачать руководство пользователя страница 24](http://html1.mh-extra.com/html/franklin-fueling-systems/guardian-spgc-220/guardian-spgc-220_installation-manual_2328975024.webp)
20
Open Circuit alarm (continued)
Go to the STP
junction box and remove
the cover.
Verify that the capacitor wiring is
correct. (Refer to SB003 for a wiring
diagram.)
Seal the junction box.
Use an ohmmeter to measure the
resistance of the red wire to the
black wire, the red wire to the
orange wire, and the black wire to
the orange wire.
A
B
C
Yes
No
Do the resistance
measurements match the
values in TB004 for the
PMA HP?