9
Selectable features
Auto Restart Mode (SW1, Pole 8)
When this mode is selected, with SW1 Pole 8 in the ON position, if the controller detects an
empty tank/under load condition, it shuts down the pump and it attempts to start the pump
when a hook signal is removed and reintroduced to the controller. If the empty tank condition is
still present, the controller shuts down the pump. If the empty tank condition is corrected (i.e.,
the tank is refilled), the controller runs the STP and clears the abnormal condition. In Primary-
Secondary configuration, if the Primary is in the under load condition, it waits until the Secondary
controller calls for help before attempting to restart. By default (SW1 Pole 8 in the OFF position),
the pump will remain shut down after a UL fault detection until you manually reset or power
cycle the controller.
Fault Shutdown Mode (SW2, Pole 1)
This is for only Primary-Secondary and AC configurations. Select this mode only on the Primary
controller (SW2 Pole 1 in the ON position) to cause the Primary and all connected Secondaries to
shut down if any controllers (Primary or Secondary) detect an abnormal condition. The Primary
and all connected Secondaries will not run until the abnormal condition is corrected and you
manually reset or power cycle the controllers. The fault shutdown is required if you are using
a Veeder-Root™ PLLD in a Primary-Secondary configuration. By deafult (SW2 Pole 1 in the OFF
position), an abnormal condition will shut down only the controller that has detected a fault.
Extended Run Disable (SW2, Pole 5)
This switch, in the ON position, disables the extended run fault detection of the SPGC-220. By
default (SW2 Pole 5 in the OFF position), the extended run fault shuts off the STP if it has been
running for 60 minutes without a change in the motor load. You might, for example, use this
switch with an emergency generator where the STP runs for extended periods at the same
product flow (motor load).
CAUTION
: Do not disable the extended run if the system requires the pump to be off for line
leak detection (i.e. mechanical leak detectors or electronic line leak detection). Disabling the
extended run fault and running the STP continuously could mask a leak in the system.
DEF Mode (SW2, Pole 6)
When this mode is selected (SW2 Pole 6 ON), the SPGC-220 with rev 0.3.8 firmware or higher
will detect abnormal conditions of FE Petro model DEF-PMA150A or DEF-PMA150B operating
in diesel exhaust fluid ONLY. By default, the SPGC-220 is intended for use with single phase
submersible turbine pumps operating in motor fuels, FE Petro and like competitive petroleum
pump motor models only
.
Содержание GUARDIAN SPGC-220.
Страница 1: ...GUARDIAN SERIES TM SINGLE PHASE CONTROLLER INSTALLATION GUIDE...
Страница 8: ...4 Intentionally Blank...
Страница 31: ...27 SPGC 220 StandAlone wiring diagram...
Страница 32: ...28 SPGC 220 Primary Secondary wiring diagram...
Страница 33: ...29 SPGC 220Alternating Circuit wiring diagram...
Страница 34: ...SPGC 220 Primary Secondary Alternating Circuit wiring diagram...
Страница 35: ...SPGC 220 replacement parts Lower power relay board Part 225005932 Upper control user input board Part 225000932...
Страница 36: ...223987103 r3...