Franklin Fueling Systems GUARDIAN SPGC-220. Скачать руководство пользователя страница 13

9

Selectable features

Auto Restart Mode (SW1, Pole 8)

When this mode is selected, with SW1 Pole 8 in the ON position, if the controller detects an 
empty tank/under load condition, it shuts down the pump and it attempts to start the pump 
when a hook signal is removed and reintroduced to the controller. If the empty tank condition is 
still present, the controller shuts down the pump. If the empty tank condition is corrected (i.e., 
the tank is refilled), the controller runs the STP and clears the abnormal condition. In Primary-
Secondary configuration, if the Primary is in the under load condition, it waits until the Secondary 
controller calls for help before attempting to restart. By default (SW1 Pole 8 in the OFF position), 
the pump will remain shut down after a UL fault detection until you manually reset or power 
cycle the controller.

Fault Shutdown Mode (SW2, Pole 1)

This is for only Primary-Secondary and AC configurations. Select this mode only on the Primary 
controller (SW2 Pole 1 in the ON position) to cause the Primary and all connected Secondaries to 
shut down if any controllers (Primary or Secondary) detect an abnormal condition. The Primary 
and all connected Secondaries will not run until the abnormal condition is corrected and you 
manually reset or power cycle the controllers. The fault shutdown is required if you are using 
a Veeder-Root™ PLLD in a Primary-Secondary configuration. By deafult (SW2 Pole 1 in the OFF 
position), an abnormal condition will shut down only the controller that has detected a fault.

Extended Run Disable (SW2, Pole 5)

This switch, in the ON position, disables the extended run fault detection of the SPGC-220. By 
default (SW2 Pole 5 in the OFF position), the extended run fault shuts off the STP if it has been 
running for 60 minutes without a change in the motor load. You might, for example, use this 
switch with an emergency generator where the STP runs for extended periods at the same 
product flow (motor load).

 

CAUTION

: Do not disable the extended run if the system requires the pump to be off for line 

leak detection (i.e. mechanical leak detectors or electronic line leak detection). Disabling the 
extended run fault and running the STP continuously could mask a leak in the system.

DEF Mode (SW2, Pole 6)

When this mode is selected (SW2 Pole 6 ON), the SPGC-220 with rev 0.3.8 firmware or higher 
will detect abnormal conditions of FE Petro model DEF-PMA150A or DEF-PMA150B operating 
in diesel exhaust fluid ONLY.  By default, the SPGC-220 is intended for use with single phase 
submersible turbine pumps operating in motor fuels, FE Petro and like competitive petroleum 
pump motor models only
.

Содержание GUARDIAN SPGC-220.

Страница 1: ...GUARDIAN SERIES TM SINGLE PHASE CONTROLLER INSTALLATION GUIDE...

Страница 2: ...of third parties that may result from use of this manual or the products We make no warranty of any kind with regard to this material including but not limited to the implied warranties of merchantab...

Страница 3: ...e 8 9 Fault Shutdown Mode SW2 Pole 1 9 Extended Run Disable SW2 Pole 5 9 DEF Mode SW2 Pole 6 9 Calibration 10 Calibration steps 10 Troubleshooting 11 Disabling the audible alarm 11 Reset11 Selectable...

Страница 4: ...e 60 Hz wiring 25 DEF PMA150B Single Phase 50 Hz wiring 26 DEF PMA150C Three Phase 50 Hz wiring 26 SPGC 220 Stand Alone wiring diagram 27 SPGC 220 Primary Secondary wiring diagram 28 SPGC 220 Alternat...

Страница 5: ...that could result in minor or moderate injury if not avoided This may also be used to alert against unsafe practices WARNING This indicates a potentially hazardous situation that could result in seve...

Страница 6: ...e designed to trap hazardous liquid spills and prevent environmental contamination so they can accumulate dangerous amounts of hydrocarbon vapors Check the atmosphere in the sump regularly while you a...

Страница 7: ...ation Supply input rating 200 250 VAC 50 60 HERTZ 14 5 AMPS Motor contact rating 200 250 VAC 50 60 HERTZ 2 HP 1 5 KW Switch hook rating 120 240 VAC 50 60 HZ 16 mA Supply motor wiring 10 14 AWG 300 V m...

Страница 8: ...4 Intentionally Blank...

Страница 9: ...e sure you provide them to anyone who services this equipment NOTE Wiring diagrams are in the Troubleshooting chapter of this manual 1 Install the STP according to its installation documentation IMPOR...

Страница 10: ...rns back on The Primary Secondary AC configuration see the SPGC 220 Primary Secondary Alternating Circuit wiring diagram combines the features of Primary Secondary and AC CAUTION Line leak detection p...

Страница 11: ...f Off On Secondary 18 Off On Off Off On Secondary 19 On On Off Off On Secondary 20 Off Off On Off On Secondary 21 On Off On Off On Secondary 22 Off On On Off On Secondary 23 On On On Off On Secondary...

Страница 12: ...lers to shut down 2 Address 1 2 Unused The default position is ON 3 Address 2 3 Primary Secondary ON designates the SPGC 220 as the Primary controller This switch must be set to OFF for Secondary and...

Страница 13: ...l condition is corrected and you manually reset or power cycle the controllers The fault shutdown is required if you are using a Veeder Root PLLD in a Primary Secondary configuration By deafult SW2 Po...

Страница 14: ...DEF MODE if applicable The factory default is SW2 Pole 6 OFF for petroleum pump motor assemblies Calibration steps 1 Close either the STP clamp valve or a ball valve at the STP discharge attach the co...

Страница 15: ...l Support for assistance If the display is flashing and the audible alarm is beeping there is an abnormal condition Note the flashing code on the display and refer to the appropriate troubleshooting t...

Страница 16: ...ON position the controller operates as a standard relay control box It will not indicate or shut down due to an abnormal condition with the exception of an over current condition The bypass mode is a...

Страница 17: ...a clogged intake or improper calibration Is the level less than 8 inches Press and hold the Reset button until the display goes blank and then release the button Determine the fuel level in the stora...

Страница 18: ...14 Underload Error alarm continued Deactivate the hook signal and Bypass Mode Recallibrate the controller Contact FFS Tech Support Monitor for proper operation Was the callibration successful A No Yes...

Страница 19: ...hen the incoming voltage returns to the acceptable range LI resets above 200V and HI resets below 245V Does the controller go into the LI error code Is the voltage between 200 and 250 VAC A No Yes Yes...

Страница 20: ...oltage equal the measured voltage within 10VAC Was the calibration successful Use the ATG Control Pumps menu to determine what the calibrated voltage of the SPGC 220 was Monitor for proper operation C...

Страница 21: ...a locked PMA rotor due to debris or damage or improper calibration Was the PMA replaced with a new PMA of the same horsepower Press and hold the Reset button until the display goes blank Release the...

Страница 22: ...wrench to manually spin the PMA rotor Replace the PMA and reinstall the extractable Does the motor spin freely Yes No Contact FFS Tech Support Turn on power to the smart controller Recalibrate the SP...

Страница 23: ...mal overload due to a locked rotor event Press and hold the Reset button Release the button when the display goes blank Monitor for proper operation Use an Ohmmeter on its lowest setting to measure th...

Страница 24: ...wiring is correct Refer to SB003 for a wiring diagram Seal the junction box Use an ohmmeter to measure the resistance of the red wire to the black wire the red wire to the orange wire and the black wi...

Страница 25: ...tors Correct or replace them as needed Activate the circuit breaker Seal all open STP junction boxes Activate the hook signal and monitor its operation Monitor for proper operation Lock and tag out ci...

Страница 26: ...t be calibrated before they can be used See Calibration in the Installation chapter of this manual for the calibration procedure Was the calibration successful Go to the troubleshooting topic for the...

Страница 27: ...xtended run disable switch SW2 pole 5 to ON Measure for voltage across the hook terminals No Does the application require the STP to run at constant flow rates for at least 60 minutes Yes Yes Monitor...

Страница 28: ...relay contact failure Press and hold the reset button until the error code lights dim Lock out and tag out the circuit breaker Release the reset button Replace the smart controller relay board Reacti...

Страница 29: ...N NOTE The lockout switch is not a substitute for properly locking out and tagging out the electrical circuit when you service this equipment NOTE You can install the single phase DEF PMA capacitor ne...

Страница 30: ...Hz 208 240 Volts NOTE The lockout switch is not a substitute for properly locking out and tagging out the electrical circuit when you service this equipment NOTE You can install the single phase DEF P...

Страница 31: ...27 SPGC 220 StandAlone wiring diagram...

Страница 32: ...28 SPGC 220 Primary Secondary wiring diagram...

Страница 33: ...29 SPGC 220Alternating Circuit wiring diagram...

Страница 34: ...SPGC 220 Primary Secondary Alternating Circuit wiring diagram...

Страница 35: ...SPGC 220 replacement parts Lower power relay board Part 225005932 Upper control user input board Part 225000932...

Страница 36: ...223987103 r3...

Отзывы: