8
Factory default switch settings
!
NOTE:
The default factory setting is the Stand Alone configuration with
all selectable features off: Fault Read out, Bypass, Auto Restart, Fault
Shutdown, and Extended Run Disable.
NOTE:
If your SPGC-220 includes the SW3 option select switch, leave all
poles in the OFF position. (This is the factory default.)
NOTE:
The Rotary Select Switch adjacent to SW3 is to be left at position
0 (factory default), unless you are instructed by FFS Tech Support to
change it. If the Rotary Select Switch is moved from position 0, there
could be calibration and operation issues with your SPGC-220.
Switch definitions
SW 1
SW 2
Pole Description
Function
Pole Description
Function
1
Address 0
Use poles 1-5 to set the
addressing switches for
Primary-Secondary or AC
configurations. See step 4 of
the "Primary-Secondary/AC"
section.
1
Fault
Shutdown
When this is ON, an abnormal condition
detected on any controller in a Primary-
Secondary or AC configuration causes all
connected controllers to shut down.
2
Address 1
2
Unused
The default position is ON.
3
Address 2
3
Primary-
Secondary*
ON designates the SPGC-220 as the
Primary controller. This switch must be
set to OFF for Secondary and Stand Alone
configurations.
4
Address 3
4
AC**
When the Primary controller is ON, the AC
feature is active. OFF indicates a Secondary
or Stand Alone configuration.
5
Address 4
5
Extended
Run
Disable***
ON disables the extended run feature. OFF
activates the extended run feature.
6
Fault
Readout*
ON activates the fault readout
function.
6
DEF Mode
ON enables use with Diesel Exhaust Fluid
submersibles (for models
DEF-PMA150A or DEF-PMA150B only).****
7
Bypass*
ON bypasses diagnostics for
10 minutes.
7
Unused
Unused switches. The default position is
OFF.
8
Auto
Restart***
When ON, the controller
tries to restart the STP after
an underload (UL) fault
condition.
8
Unused
* See the "Troubleshooting" chapter for more information.
** See step 3 of the "Primary-Secondary/Alternating Circuit" section for configuration switch settings.
*** See the "Installation" chapter for details.
**** DEF Mode is available only with SPGC-220 revision 0.3.8 firmware or higher. (The firmware revision is shown when the
controller starts up and resets.)
Содержание GUARDIAN SPGC-220.
Страница 1: ...GUARDIAN SERIES TM SINGLE PHASE CONTROLLER INSTALLATION GUIDE...
Страница 8: ...4 Intentionally Blank...
Страница 31: ...27 SPGC 220 StandAlone wiring diagram...
Страница 32: ...28 SPGC 220 Primary Secondary wiring diagram...
Страница 33: ...29 SPGC 220Alternating Circuit wiring diagram...
Страница 34: ...SPGC 220 Primary Secondary Alternating Circuit wiring diagram...
Страница 35: ...SPGC 220 replacement parts Lower power relay board Part 225005932 Upper control user input board Part 225000932...
Страница 36: ...223987103 r3...