©2013 FFS 400289002 Rev. 9
19. Connect power to the submersible pump at the electrical supply box.
20. Test proper operation by dispensing product into calibration can.
21. Turn off the dispenser switch. Feel the submersible pump, to make sure that the pump has stopped running.
Note:
If the pump does not turn off when the dispenser switch is turned off, this may indicate an electrical problem in the
dispenser or other wiring error or malfunction. Call this to the immediate attention of a qualified electrician.
22. Visually check for leaks on the manifold head during pump operation and after.
23. To ensure that the STP is providing proper line pressure, install a pressure gauge in the line test port. Turn on the
STP and, while it’s running, the pressure should be above 24 psi (1.65 bar) (PMA size will affect psi). Turn off the
STP and verify that the line pressure is holding. Remove the pressure gauge, replace the plug, turn on the STP and,
again, visually check for any leaks.
24. If any leaks are observed, line pressure isn’t correct, or any other problems or concerns occur, call FFS Technical
Support at 1-800-225-9787.
25. Fill out the Warranty Registration Card and return it to Franklin Fueling Systems.
Note:
If a STP or an IST does not operate correctly or there are any questions concerning installation or service, please
contact FFS Technical Services at (800) 225-9787.