SPECIFICATIONS
53
SPECIFICATIONS
User Interface
Settings Adjustments
32 character, backlight NEMA 4X display
FE Connect mobile app connected via Bluetooth
Hand/Off/Auto
Door mounted 3-position switch
Standard Control Operations
Input
Power Supply
200-600 VAC, 50-60 Hz
Current Range
1-135 A
PT100/1000
(1 or 2 channels) 24 VAC, 10 mA max. - On/Off, adjustable: 32-212 °F (0-100 °C)
RS-485
Modbus RTU Slave
Voltage Inputs (wet)
(MT1311 and MT2211 only) (1 or 2 channels) 12-250 VAC, 5 mA max.
Output
Fault Relay Output,
Dry Output
Normally Open Relay Contact: 1A @ 240VAC
Voltage
Current
Load Type
110 VDC
0.30
Resistive, General Purpose
125 VDC
0.50
General Purpose
30 VDC
2.00
Resistive, General Purpose
120 VAC
0.50
Resistive
125 VAC
1.00
General Purpose
240 VAC
0.25
Resistive
Control Circuit (TRIAC) to
contactor
(MT1111, MT6111, MT1311
only)
C600 Pilot Duty (120 VAC, 1.5 A | 240 VAC 0.75A | 480 VAC, 0.37 A | 600 VAC, 0.30A)
RS485
5 VDC
Pilot Device and Dry
Inputs (MT1311 and MT2211
only)
1, 2, 3, or 4 @ 24 VDC, 10 mA maximum
PWM Connector C+, C-
(MT2111 only)
24Vdc, 229 VA inrush, 21 VA max holding. Worst case ratings for connected UL contactors.
Operational
Overload Types
Electronic, simulated I
2
T trip curve
Impulse Rating
6 KV
Enclosure
UL Type 3R Open Industrial Control - Type 1 (IP20).
External display - Type 4X is mounted on a panel or enclosure.
Overload Overvoltage
Category
Category III
Overload Pollution
Degree
Degree 2
Power Fail Modes
Restart in last mode (Hand/Off/Auto)
Restart in Off mode
Minimum Off Timer
(Backspin Delay)
On/Off, adjustable: 2 seconds to 60 minutes
Fault Reset
Adjustable: manual or automatic (default differs per motor protection feature chosen)
Starts
6/hour, 20 seconds max start time @ 400% FLA, 30 seconds max start time @ 300% FLA
Short Circuit Rating
600 VAC, 200,000 amps (units have internal CTs)
Dimensions / Weight
4 ¾ x 4
⅞
x 4 ½ in (120.7 x 123.7 x 114.5 mm) / 2 lbs. (0.91 kg)
Содержание SUBMONITOR CONNECT MT1111
Страница 1: ...franklinwater com SUBMONITORCONNECT Installation and Operation Manual ...
Страница 60: ...SPECIFICATIONS Wiring Diagrams for Panels 60 Standard SMS Panel Using Current Transformers 200 480VAC MT1311 ...
Страница 61: ...SPECIFICATIONS Wiring Diagrams for Panels 61 Standard SMS Panel Using Current Transformers 600VAC MT1311 ...
Страница 62: ...SPECIFICATIONS Wiring Diagrams for Panels 62 Standard SMS Panel with PWM Contactor Output MT2211 ...
Страница 63: ...SPECIFICATIONS Wiring Diagrams for Panels 63 Reduced Voltage SMS Panel with Relay Contactor Output MT1311 ...
Страница 66: ...SPECIFICATIONS Wiring Diagrams for Panels 66 Reduced Voltage SMS Panel with PWM Contactor Output MT2211 ...
Страница 72: ...800 348 2420 franklinwater com For technical assistance please contact Form 250001701 Rev 002 06 19 ...
Страница 73: ...ESPAÑOL ES franklinagua com SUBMONITORCONNECT Manual de instalación y funcionamiento ...
Страница 142: ...ESPECIFICACIONES Diagramas de cableado para paneles 70 Panel SMS estándar con salida de contactor PWM MT2211 ...
Страница 146: ...ESPECIFICACIONES Diagramas de cableado para paneles 74 Panel SMS de voltaje reducido con salida de contactor PWM MT2211 ...
Страница 152: ...800 348 2420 franklinagua com Para la ayuda técnica por favor póngase en contacto Form 250001701 Rev 002 06 19 ...
Страница 153: ...franklinwater com FRANÇAIS FR SUBMONITORCONNECT Manuel d installation et d utilisation ...
Страница 220: ...SPÉCIFICATIONS Diagrammes de câblage pour les panneaux 68 Panneau SMS standard avec sortie de contacteur PWM MT2211 ...
Страница 229: ...NOTES 77 NOTES ...
Страница 230: ...NOTES 78 NOTES ...
Страница 232: ...800 348 2420 franklinwater com Pour l aide technique entrez s il vous plaît en contact Form 250001701 Rév 002 06 19 ...