INSTALLATION AND SETUP
Start-Up Programming
15
5. Connect each CT wire to it’s other CT wire via the grounded terminal block (inset photo on previous
page).
CT Kits available:
•
5860015170 - SubMonitor Connect CT Kit, 120-270A
•
5860015180 - SubMonitor Connect CT Kit, 200-400A
•
5860015210 - SubMonitor Connect CT Kit, 320-720A
•
5860015190 - SubMonitor Connect CT Kit, 400-900A
When using CTs as part of the SubMonitor Connect system, be sure to program the SubMonitor Connect
appropriately. Refer to
“Programming: Advanced Setup > Administration” on page 26
for External CT Ratio
setup, or make this setting using the FE Connect mobile app.
An example for CT use:
An installation is using 500:5 ratio CTs with 500 A on the power lines.
The SubMonitor Connect measures 5 A. The SubMonitor Connect resolution is 0.1 A, which equates to ±10 A
reading on the motor power lines. This means that the SubMonitor Connect reading difference can be
between 505 A and 495 A.
Refer to
“Wiring Diagrams for Panels” on page 59
for schematics.
Start-Up Programming
Using the Control Interface
1.
Display:
Shows system status information
and programming menu items.
2.
SHIFT:
Press SHIFT to move the blinking
cursor left one position for each button
press. When the cursor reaches the left-
most editable position, another SHIFT
button press moves the cursor to the
right-most position of the parameter.
3.
UP
and
DOWN:
Use to navigate menus
and adjust parameters.
4.
ENTER:
Executes menu selection and con
-
firms any changes made to parameter
settings. Also allows user to access sub-
menus and selected parameters.
5.
ESC:
Pressing the ESC button moves the menu back one level.
6.
Run LED:
This green LED lights to alert the user to water flow (the pump motor is running).
7.
Fault LED:
Off (when not lighted) indicates normal operation. A blinking LED indicates the measured
current is higher than the Overload setting, and will trip soon if the condition persists. A solid on LED
indicates an active fault condition.
Remove the detachable display for access to these items:
TEST/RESET:
Pressing this button resets a fault condition, if present. In a non-fault condition, pressing
this button puts the SubMonitor Connect into a fault state.
Содержание SUBMONITOR CONNECT MT1111
Страница 1: ...franklinwater com SUBMONITORCONNECT Installation and Operation Manual ...
Страница 60: ...SPECIFICATIONS Wiring Diagrams for Panels 60 Standard SMS Panel Using Current Transformers 200 480VAC MT1311 ...
Страница 61: ...SPECIFICATIONS Wiring Diagrams for Panels 61 Standard SMS Panel Using Current Transformers 600VAC MT1311 ...
Страница 62: ...SPECIFICATIONS Wiring Diagrams for Panels 62 Standard SMS Panel with PWM Contactor Output MT2211 ...
Страница 63: ...SPECIFICATIONS Wiring Diagrams for Panels 63 Reduced Voltage SMS Panel with Relay Contactor Output MT1311 ...
Страница 66: ...SPECIFICATIONS Wiring Diagrams for Panels 66 Reduced Voltage SMS Panel with PWM Contactor Output MT2211 ...
Страница 72: ...800 348 2420 franklinwater com For technical assistance please contact Form 250001701 Rev 002 06 19 ...
Страница 73: ...ESPAÑOL ES franklinagua com SUBMONITORCONNECT Manual de instalación y funcionamiento ...
Страница 142: ...ESPECIFICACIONES Diagramas de cableado para paneles 70 Panel SMS estándar con salida de contactor PWM MT2211 ...
Страница 146: ...ESPECIFICACIONES Diagramas de cableado para paneles 74 Panel SMS de voltaje reducido con salida de contactor PWM MT2211 ...
Страница 152: ...800 348 2420 franklinagua com Para la ayuda técnica por favor póngase en contacto Form 250001701 Rev 002 06 19 ...
Страница 153: ...franklinwater com FRANÇAIS FR SUBMONITORCONNECT Manuel d installation et d utilisation ...
Страница 220: ...SPÉCIFICATIONS Diagrammes de câblage pour les panneaux 68 Panneau SMS standard avec sortie de contacteur PWM MT2211 ...
Страница 229: ...NOTES 77 NOTES ...
Страница 230: ...NOTES 78 NOTES ...
Страница 232: ...800 348 2420 franklinwater com Pour l aide technique entrez s il vous plaît en contact Form 250001701 Rév 002 06 19 ...