QUICKSTART GUIDE

Troubleshooting

11

Troubleshooting

Diagnostic Fault Codes

Code Reset

Fault

Possible Cause

Corrective Action

F1

Auto

Motor Underload

• Over-pumped well
• Broken shaft or coupling
• Blocked screen, worn pump
• Air/gas locked pump
• Underload Sensitivity setting 

incorrect

• Frequency near maximum with load less than configured ULD 

sensitivity

• System is drawing down to pump inlet (out of water)
• High static, light loading pump - reset for less sensitivity if not out of 

water

• Check pump rotation, reconnect if necessary for proper rotation
• Air/gas locked pump - if possible, set deeper in well to reduce

F2

Auto

Undervoltage

• Low line voltage
• Misconnected input leads
• Loose connection at breaker or panel

• Line voltage low,
• Check incoming power connections and correct or tighten if necessary
• Correct incoming voltage - check breaker or fuses, contact power 

company

F3

Auto

Overcurrent or

Locked Pump

• Motor and/or pump locked
• Abrasives in pump
• Excess motor cable length

• Amperage above SFL at 30 Hz
• Remove and repair or replace as required
• Reduce motor cable length. Adhere to Maximum Motor Cable Length 

table.

F5

Manual Open Phase

• Loose connection
• Defective motor or drop cable
• Wrong motor

• Open reading on DC test at start.
• Check drop cable and motor resistance, tighten output connections. 
• Use dry motor to check drive functions. 

F6

Manual Short Circuit

• When fault is indicated immediately 

after power-up, short circuit caused 
by a shorted connection, defective 
cable, splice or motor

• Amperage exceeded 25 amps on DC test at start or SF amps during 

running

• Incorrect output wiring, phase to phase short, phase to ground
• If fault is present after resetting and removing motor leads, replace 

drive

F7

Auto

Overheated Drive

• High ambient temperature
• Direct sunlight
• Obstruction of airflow

• Fan blocked or inoperable, ambient above 122 °F (50 °C), direct 

sunlight

• Replace fan or relocate drive as necessary
• Remove debris from fan intake/exhaust

F9

Manual Internal PCB Fault

• A fault was found internal to drive

• Contact Technical Service

F12

Auto

Overvoltage

• High line voltage
• Internal voltage too high

• Check incoming power connections and correct or tighten if necessary
• If line voltage is stable and within range, contact Technical Service

F14

Manual Broken Pipe

• Broken pipe or large leak is detected
• Drive runs at full power for 10 

minutes without reaching pressure 
setpoint

• Large water draw does not allow 

system to reach pressure setpoint

• Check system for large leak or broken pipe
• If the system contains a sprinkler system or is being used to fill a pool 

or cistern, disable the Broken Pipe Detection

F15

Manual Phase Imbalance

• Motor phase currents differ by >20%
• Motor is worn internally
• Motor cable resistance is not equal
• Incorrect motor phase setting 

• Check resistance of motor cable and motor windings
• Verify motor type matched drive settings (single- or three-phase)

F16

Manual Ground Fault

• Motor cable is damaged
• Phase to ground short

• Check motor cable insulation resistance with megger (while not 

connected to drive). Replace motor cable if needed.

F25

Manual Moisture Sensor 

Fault

• Moisture or water detected
• Input is incorrectly configured

• Check Moisture Sensor location for moisture or presence of water. 
• Ensure Moisture Sensor input is configured correctly

F27

Auto

Pressure Trans

-

ducer Error

• Transducer has failed
• Transducer is incorrectly wired
• Transducer signal is out of range
• Transducer is disconnected
• Incorrect sensor type setting

• Check pressure transducer wiring connections
• Ensure sensor type setting is correct
• Replace pressure transducer

Содержание SubDrive Connect Plus SDCP-SUB1023

Страница 1: ...arger than the outer dimensions of the enclosure in order to maintain the NEMA 3R rating NEMA 3R enclosures are capable of withstanding downward directed rain only Protect from hose directed or sprayed water as well as blowing rain Failure to do so may result in controller failure Install away from direct sunlight or locations subject to extreme temperatures or humidity Pressure Tank Sizing A VFD ...

Страница 2: ...race IMPORTANT Do not drill holes in the drive Risk of bodily injury or damage to drive or other equipment The drive must be mounted on a heat resistant back plate Ensure suitable mounting hardware is used when installing back plate and drive on drywall Use suitable lifting equipment in good condition rated for at least 5 times the weight of the drive 692 mm 27 24 in 523 55 mm 20 61 in 658 5 mm 25...

Страница 3: ...rrents caused by parallel wiring or close proximity between high voltage and control wiring can cause unexpected behaviors Do not run input power and motor wires in the same conduit Do not run motor wires from multiple VFDs in common conduit Do not run control wiring parallel with high voltage wiring Do not install a magnetic contactor or disconnect in the motor circuit Do not run VFD wiring paral...

Страница 4: ... be less than or equal to 253 V If line to line voltage exceeds these ratings the drive cannot be used on the incoming power supply An additional suitably sized transformer will be required to bring the voltages within limits If line to ground voltage exceeds these ratings remove both pins of EMC jumper J10 1 2 3 4 Contact with hazardous voltage could result in death or serious injury Disconnect a...

Страница 5: ...center of the drive large opening and connect them to the terminal block posi tions marked Ground Red W Yellow V and Black U For drives that include an output filter motor connections are made at the termi nal block on the left side of the filter In this case the terminals are marked Ground Red U Yellow V and Black W These terminals accept wire sizes from 2 to 20 AWG and can be tightened to 31 in ...

Страница 6: ...e connection for voltage sensing circuit for two three and four wire PT100 PT1000 RTD sensors I V Negative connections for the excitation and voltage sensing circuits for two three and four wire PT100 PT1000 RTD sensors 6 Moisture Sensor The WET SENSOR terminal supports the Franklin Electric Moisture Sensor Connect the red cable lead to the 24 terminal Connect the black cable lead to the terminal ...

Страница 7: ...tion NOTE Submersible Motor Type will not allow 8 kHz Analog Output Selection DIP SW1 Position 4 Use this switch to select the signal to be repeated on the 4 20mA Out terminal The analog output repeats the 4 20mA tranducer reading when the switch is in the off down position The analog output is proportional to the motor speed value when the switch is in the on up position Bump Mode Configuration D...

Страница 8: ...d on the motor nameplate Sensor Type Configures the drive for the type of pressure transducer or sensor being used Selecting Trans ducer displays the Sensor Range screen If a standard Pressure Sensor is selected the System Response screen is dis played Sensor Range Scales system operation to the installed transducer The default setting is 200 psi Setpoint 1 When using a Pressure Transducer use thi...

Страница 9: ...n Underload is detected properly If the system does not trip as it should adjust to a higher sensitivity setting Underload Off Time This setting determines how long the drive will wait before attempting to run after an Underload event The default time is five minutes but is user adjustable from one minute to 48 hours QR Code This screen displays a code identifying the drive for connection to the m...

Страница 10: ...R Code Sticker or Enter the Bluetooth Key 3 If using the scanning tool center the QR code on the drive in the screen If the code is missing or unreadable the code can be displayed on the screen Refer to Menu Navigation on page 8 4 If using the Bluetooth key also available onscreen 5 Enter a Name and Location to identify the drive within the app 6 Tap Finish Connect to complete the connection Using...

Страница 11: ...s replace drive F7 Auto Overheated Drive High ambient temperature Direct sunlight Obstruction of airflow Fan blocked or inoperable ambient above 122 F 50 C direct sunlight Replace fan or relocate drive as necessary Remove debris from fan intake exhaust F9 Manual Internal PCB Fault A fault was found internal to drive Contact Technical Service F12 Auto Overvoltage High line voltage Internal voltage ...

Страница 12: ...tion Use caution when contacting surfaces Operation of this equipment requires detailed installation and operation instructions provided in this manual for use with this product Read entire manual before starting installation and operation End User should receive and retain manual for future use Keep safety labels clean and in good condition High voltages capable of causing severe injury or death ...

Отзывы: