OPERATION TESTING
Testing Manual Pump Operation
8
Testing Manual Pump Operation
Pumps with -CIM in the model name are manual pumps.
The 9EC-CIM, 9ECH-CIM, and 10ECH-CIM manual pumps do not include an automatic liquid level control.
The pump cord for these pumps can be plugged directly into a properly grounded receptacle with voltage
consistent with the pump nameplate for continuous pump operation.
For automatic operation of a manual pump, a separate float switch or other liquid level control may be used.
If a float switch or level control has been added, refer to
“Testing Automatic Pump Operation” on page 7
for
testing operation.
To test manual pump operation, follow these steps:
1.
Connect a discharge hose to the pump's discharge port.
2. Place pump into a basin or test reservoir.
3. Direct the opposite end of the discharge hose back into the basin or test reservoir so that the water dis
-
charged from the hose during testing will be contained within the basin or test reservoir. Secure the
hose to prevent the water pressure created during testing from causing the hose to exit the basin or
test reservoir.
4. If there is a valve on the discharge hose, be sure the valve is open.
5. Using a separate water source, fill the basin or test reservoir until the pump is fully submerged. Do not
attempt to run the pump without water; this could result in permanent damage to the pump. Do not
overfill the basin or test reservoir.
6. If the pump is provided with an attachment plug on the power cord, plug the pump's power cord into a
ground fault circuit interrupter (GFCI) receptacle with voltage consistent with the pump voltage, as
indicated on the pump nameplate.
If the pump is hardwired, turn on the circuit breaker for the pump's power circuit.
7. Confirm that the pump is functioning as intended.
NOTE
: It is normal for a stream of water to spray from the air bleed hole in the pump's plumbing. Con
-
firm that this spray is captured within the basin.
8. If pump is not functioning as intended, disconnect power from the pump and refer to
. If the solution still cannot be found, please contact the place of purchase or an autho
-
rized service center.
9. If the pump is functioning as intended, disconnect power from the pump before attempting to remove
it from the basin or test reservoir.
Risk of bodily injury or damage to pump or other equipment.
•
Manual, continuous pump operation should be used only for emergencies, or when a large volume
of water is to be pumped. The pump must be continuously monitored during operation and
disconnected from power before the pump runs dry.
•
If an accessory float switch or other liquid level control is installed, refer to manufacturer’s
instructions. Failure to install control in compliance with national and local electrical and plumbing
codes and within manufacturer’s recommendations may result in electrical shock or fire hazard,
unsatisfactory performance, or equipment failure.