COMMUNICATIONS
BACnet Communication
93
Status Binary Value Objects (Read Only)
Object Number
R/W
Object Name
Object Description
BV 016
R At CMD Freq
0_Out Frq
?
CMD
Frq1_Out Frq = CMD Frq
BV 017
R Direction
0_Forward
1_Reverse
BV 018
R Warning
0_None
1_Warning Active
BV 019
R Error/Fault
0_None
1_Error/Fault Active
BV 020 through BV 021
R Reserved
–
BV 022
R Q-Stop Mode
0_None
1_Q-Stop Active
BV 023
R Power OUT
0_Power OUT Off
1_Power OUT On (Run)
BV 024 through BV 031
R Reserved
–