COMMUNICATIONS
BACnet Communication
92
Commandable Binary Value Objects
AV 053
R PID F/B Value
PID Feedback Value
%
AV 054
R Overload Rate
Overload Value
%
AV 055
R GND Fault Level
Ground Fault Trip Level
%
AV 056
R DC Bus Ripples
DC Bus Ripples Amplitude
Volts
AV 057
R Fan Speed
VFD Cooling Fan Speed
%
AV 058
R Motor Speed
Actual Motor Speed
RPM
AV 059
R kWh
Kilowatts per hour
kWh
AV 060
R Step Frequency
Step Frequency ID number
–
AV 061
R AVI1 Input Value
AVI1 Analog Input Reading
%
AV 062
R ACI Input Value
ACI Analog Input Reading
%
AV 063
R AVI2 Input Value
AVI2 Analog Input Reading
%
AV 064
R Digital IN Status
Digital Inputs Status [IO–46]
–
AV 065
R Digital OUT Status
Digital Outputs Status [IO–58]
–
AV 066
R CPU DI Pin Status
CPU Pins from Digital INs Status
–
AV 067
R CPU DO Pin Status
CPU Pins to Digital OUTs Status
–
AV 068
R PLC D1043 Status
PLC Register D1043 Status
–
Object Number
R/W
Object Name
Object Description
Unit
Object Number
R/W
Object Name
Object Description
BV 000
RW Freq Active CMD
0_Frq CMD=0Hz
1_Frq CMD= FreqRefValue
BV 001
RW FWD/REV CMD
0_Forward
1_Reverse
BV 002
RW Reserved
–
BV 003
RW Stop CMD
0_None
1_Stop (Decelerate to 0Hz)
BV 004
RW Hold SPD
0_None
1_Stay at Current Frequency
BV 005
RW Reserved
–
BV 006
RW Q-Stop CMD
0_None
1_Quick Stop
BV 007
RW Power Out CMD
0_Power OFF (Coast to Stop)
1_Power ON (Run)
BV 008 through BV 014
RW Reserved
–
BV 015
RW Reset
0_None
1_Reset Fault
Содержание Cerus X-Drive
Страница 1: ...franklin electric com ENGLISH EN CERUSX DRIVE Installation and Operation Manual Firmware Version 1 1 ...
Страница 2: ......
Страница 3: ...CERUS X DRIVE INSTALLATION AND OPERATION MANUAL Firmware Version 1 1 Franklin Electric Co Inc ...
Страница 94: ...COMMUNICATIONS BACnet Communication 94 ...
Страница 98: ...ACCESSORIES Optional Extension Cards 98 Frame D Frame E Frame F ...
Страница 99: ...ACCESSORIES Optional Extension Cards 99 Frame G Frame H ...
Страница 102: ...ACCESSORIES Optional Extension Cards 102 ...