ELECTRICAL INSTALLATION
Control Circuit Connections
41
Control Circuit Connections
Terminal Identification
The control board is divided into 5 groups of terminals and connectors, plus a group of micro switches that
control individual terminal configurations.
•
Always insulate bare control or shield wires with shrink tubing or electrical tape to prevent short circuit.
•
The ideal length of stripped wire for control terminals is 5 mm.
1.
Analog Inputs/Outputs
– These connections are used for transducers, sensors, and control systems
such as a BAS, BMS, or PLC. Use shielded cable with shield connected to the ground terminal. Ter
-
minals accept 26~16 AWG (0.13~1.3mm
2
) wires, and should be tightened to a torque of 1.73 lb-in (0.19
Nm).
•
ACI
is a 0-10 VDC or 4-20 mA input, adjustable by micro switch. Set
[IO–00]
to match the switch
setting. Default = 4-20 mA.
•
AVI1
is a 0-10 VDC or 4-20 mA input, adjustable by micro switch. Set
[IO–05]
to match the switch
setting. Default = 0-10 V.
•
AVI2
is a 0-10VDC input.
When an input source has been connected, select the appropriate terminal in either
Auto Speed Ref
[SET
–
07]
,
Hand Speed Ref [SET
–
09]
, or
PID F/B Source [SET
–
18]
.
•
AFM1 & AFM2
are programmable, multi-function analog outputs. Refer to
[IO–59]
and
[IO–61]
for
options. Each output can be set by micro switch to 0-10V (min load 5k Ω at 2 mA) or 0/4-20 mA
(max load 500 Ω).
•
+10V
terminal (with common ACM) provides a +10 VDC 50 mA power supply for input devices.
•
ACM
terminals are the common for analog inputs, outputs and +10 VDC power supply. All ACM ter
-
minals are connected internally.
IMPORTANT:
DCM and ACM terminals are isolated from each other and from the ground. Do not
connect these terminals to earth ground, which can cause electrical noise in control circuits and
unstable VFD operation.
0-10V
0 -10V
O pen
120
AFM 1
AFM 2
AVI 1
ACI
0/4-20mA
0/4-20mA
4-20mA
4-20mA
485
RC3
RA3
RC2
RA2
RC1
RB1
RA1
AFM1 +10V
AVI1 ACI
STO1 STO2 +24
AFM2 ACM
AVI2
ACM
SCM1 SCM2 DCM
+24V COM FWD
MI1
MI3
MI5
MI7
0-10V
0-10V
SGND
DCM
REV
MI2
MI4
MI6
MI8
SG+
SG–
1
2
3
5
4
8 1
8 1
Содержание Cerus X-Drive
Страница 1: ...franklin electric com ENGLISH EN CERUSX DRIVE Installation and Operation Manual Firmware Version 1 1 ...
Страница 2: ......
Страница 3: ...CERUS X DRIVE INSTALLATION AND OPERATION MANUAL Firmware Version 1 1 Franklin Electric Co Inc ...
Страница 94: ...COMMUNICATIONS BACnet Communication 94 ...
Страница 98: ...ACCESSORIES Optional Extension Cards 98 Frame D Frame E Frame F ...
Страница 99: ...ACCESSORIES Optional Extension Cards 99 Frame G Frame H ...
Страница 102: ...ACCESSORIES Optional Extension Cards 102 ...