PHYSICAL INSTALLATION
Environmental Requirements
17
PHYSICAL INSTALLATION
Environmental Requirements
The VFD must be installed and used in a controlled environment that meets the following requirements:
The drive electronics are air-cooled. Provide
enough clearance for airflow around the VFD. See
minimum mounting clearance table below for dif
-
ferent VFD frame sizes.
Mount VFD vertically (top up) for proper heat dis
-
sipation.
Do not mount VFD in direct sunlight or near other
heat sources.
Do not block cooling vents or airflow with any
panel components or wires. Prevent debris from
adhering to the heat sink.
*
For frames sizes D, E, & F, install a metal separator between side-by-side drives. Barrier depth must match the VFD
depth.
Risk of damage to VFD
,
or malfunction can occur due to improper handling,
installation, or environment.
•
Do not mount VFD on equipment with excessive vibration.
•
Install in a location where temperature is within the range of product rating.
•
Do not mount VFD in direct sunlight or near other heat sources.
•
The VFD should be mounted in a Pollution Degree 2 environment. If VFD will be installed in an envi
-
ronment with a high probability of dust, metallic particles, mists, corrosive gas or other contami
-
nants, the VFD must be mounted inside an appropriate electrical enclosure with proper NEMA, UL
Type, or IP rating and adequate cooling.
•
When two or more VFDs are installed in a ventilated enclosure, the cooling system should provide
adequate airflow for all the VFDs. Do not install VFD above another heat source (another VFD,
inductive reactors, etc.).
Ambient Temperature
50 °C (122 °F) UL Open Type/IP20 (Top cover must be removed.)
40 °C (104 °F) in NEMA 1 / UL Type 1 / IP20 enclosure.
Location
Pollution Degree 2 Environment.
Altitude
1000m (3281 ft) above sea level. De-rate current 1% per 100 m (328 ft) from 1000 to 2000 m (3281-
6562ft). Consult Technical Support for installations above 2000 m.
Relative Humidity
95% Maximum relative humidity (non-condensing)
Vibration
1.0mm, peak to peak value range from 2 Hz to 13.2 Hz
0.7G-1.0G range from 13.2 Hz to 55 Hz
1.0G range from 55 Hz to 512 Hz.
A
A
B
B
C
D
Frame Size
A
B
C
*
D
A, B, & C
60 mm/2.4 in.
30 mm/1.2 in.
30 mm/1.2 in.
0 mm/0.0 in.
D, E, & F
100 mm/3.9 in.
50 mm/2.0 in.
100 mm/3.9 in. total 0 mm/0.0 in.
G
200 mm/7.9 in.
100 mm/3.9 in.
200 mm/7.9 in.
0 mm/0.0 in.
H
350 mm/ 13.8 in.
0 mm/0.0 in.
0 mm/0.0 in.
200 mm/7.9 in.
Содержание Cerus X-Drive
Страница 1: ...franklin electric com ENGLISH EN CERUSX DRIVE Installation and Operation Manual Firmware Version 1 1 ...
Страница 2: ......
Страница 3: ...CERUS X DRIVE INSTALLATION AND OPERATION MANUAL Firmware Version 1 1 Franklin Electric Co Inc ...
Страница 94: ...COMMUNICATIONS BACnet Communication 94 ...
Страница 98: ...ACCESSORIES Optional Extension Cards 98 Frame D Frame E Frame F ...
Страница 99: ...ACCESSORIES Optional Extension Cards 99 Frame G Frame H ...
Страница 102: ...ACCESSORIES Optional Extension Cards 102 ...