SPECIFICATIONS
575~690V Class 150~700HP (160~522kW)
146
575~690V Class 150~700HP (160~522kW)
1
UL Open Type VFD with installed UL Type 1 kit.
2
The VFD cannot produce output voltage greater than input voltage.
3
Variable torque (VT) motor rating based on a 120% overload for 1 minute. Constant Torque (CT) motor rating based
on 120% overload for 1 minute and 160% overload for 3 seconds.
Model (CXD-xxx-6V)
UL Type 1
(1)
180A
220A
290A
350A
430A
465A
590A
675A
Frame Size
F
G
H
Input Rat
-
ings
Voltage
525 (-15%) ~ 690 VAC (+10 %)
Frequency
50/60 Hz (± 5 %)
Output Rat
-
ings
Max Carrier Freq
2-9kHz
Voltage
(2)
525 ~ 690 VAC
(2)
Frequency
0.01 ~ 599 Hz
Efficiency
97 %
98 %
Power Factor
>0.98
Weight kg (lbs.)
88± 1.5 (194± 3.3)
135 ± 4 (297.6 ± 8.8)
243 ± 5 (535.7 ± 11)
DC Choke
Built-in 3%
VFD Ratings with 3-Phase Input Power
Variable
Torque
Motor
(3)
Ratings
Max Amps
180
220
290
350
430
465
590
675
Capacity [kVA]
215
263
347
418
494.5
534.7
678.5
776
Max HP @ 575V
Surface Motor
150
200
300
350
450
450
600
700
Max HP @ 575 V
8” Submersible
125
175
200
–
–
–
–
–
Constant
Torque
Motor
(3)
Ratings
Max Amps
150
180
220
290
350
430
465
590
Capacity [kVA]
179
215
239
347
402.5
442.7
534.7
776
Max HP @ 575 V
150
150
200
300
350
450
450
600
Содержание Cerus X-Drive
Страница 1: ...franklin electric com ENGLISH EN CERUSX DRIVE Installation and Operation Manual Firmware Version 1 1 ...
Страница 2: ......
Страница 3: ...CERUS X DRIVE INSTALLATION AND OPERATION MANUAL Firmware Version 1 1 Franklin Electric Co Inc ...
Страница 94: ...COMMUNICATIONS BACnet Communication 94 ...
Страница 98: ...ACCESSORIES Optional Extension Cards 98 Frame D Frame E Frame F ...
Страница 99: ...ACCESSORIES Optional Extension Cards 99 Frame G Frame H ...
Страница 102: ...ACCESSORIES Optional Extension Cards 102 ...