SPECIFICATIONS
575~690V Class 1~150HP (1.5~175kW)
145
575~690V Class 1~150HP (1.5~175kW)
1
UL Open Type VFD with installed UL Type 1 kit.
2
The VFD cannot produce output voltage greater than input voltage.
3
Variable torque (VT) motor rating based on a 120% overload for 1 minute. Constant Torque (CT) motor rating based
on 120% overload for 1 minute and 160% overload for 3 seconds.
Model (CXD-xxx-6V)
UL Type 1
(1)
003A 004A 006A 009A 012A 018A 024A 030A 036A 045A 054A 067A 086A 104A 125A 150A
Frame Size
A
B
C
D
E
Input Ratings
Voltage
525 (-15%) ~ 600 VAC (+10 %)
Frequency
50/60 Hz (± 5 %)
Output Ratings
Max Carrier Freq
2-15kHz
2-9kHz
Voltage
(2)
525 ~ 600 VAC
(2)
Frequency
0.01 ~ 599 Hz
Efficiency
97 %
98 %
97 %
Power Factor
>0.98
Weight kg (lbs.)
3 ± 0.3 (6.6 ± 0.7)
4.8 ± 1 (10.6 ± 2.2)
10 ± 1.5 (22 ± 3.3)
39 ± 1.5 (86 ±
3.3)
61 ± 1.5 (134.5 ± 3.3)
DC Choke
None
Built-in 3%
VFD Ratings with 3-Phase Input Power
Variable
Torque
Motor
(3)
Ratings
Max Amps
3
4.3
6.7
9.9
12.1
18.7
24.2
30
36
45
54
67
86
104
125
150
Capacity [kVA]
3
4.3
6.7
9.9
12.1
18.6
24.1
36
43
54
65
80
103
124
149
179
Max HP @ 575V
Surface Motor
2
3
5
7.5
10
15
20
25
30
40
50
60
75
100
125
150
Max HP @ 575 V
4” Submersible
1.5
2
3
5
7.5
10
15
–
–
–
–
–
–
–
–
–
Max HP @ 575 V
6” Submersible
–
–
–
7.5
7.5
10
20
25
25
30
40
50
60
–
–
–
Max HP @ 575 V
8” Submersible
–
–
–
–
–
–
–
–
–
–
40
50
75
75
100
100
Constant
Torque
Motor
(3)
Ratings
Max Amps
2.5
3.6
5.5
8.2
10
15.5
20
24
30
36
45
54
67
86
104
125
Capacity [kVA]
2.5
3.6
5.5
8.2
10
15.4
19.9
29
36
43
54
65
80
103
124
149
Max HP @ 575 V
1.5
2
3
5
7.5
10
15
20
25
30
40
50
60
75
100
125
VFD Ratings with 1-Phase Input Power
Variable
Torque
Motor
Ratings
Max Amps
1.5
2.15
3.35
4.95
6.05
9.35
12.1
15
18
22.5
17.82
22.11
28.3
–
–
–
Max HP @ 575V
Surface Motor
.75
1
2
3
3
7.5
10
10
15
20
15
20
25
–
–
–
Max HP @ 575 V
4” Submersible
.5
1
2
3
3
5
7.5
10
10
15
–
–
–
–
–
–
Max HP @ 575 V
6” Submersible
–
–
–
–
–
5
7.5
10
10
15
10
15
20
–
–
–
Max HP @ 575 V
8” Submersible
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
Constant
Torque
Motor
Ratings
Max Amps
1.25
1.8
2.75
4.1
5
7.7
9.95
10
12
15
18
14.8
17.8
22.1
–
–
Max HP @ 575 V
.5
1
2
3
3
5
7.7
7.5
10
10
15
10
15
20
–
–
Содержание Cerus X-Drive
Страница 1: ...franklin electric com ENGLISH EN CERUSX DRIVE Installation and Operation Manual Firmware Version 1 1 ...
Страница 2: ......
Страница 3: ...CERUS X DRIVE INSTALLATION AND OPERATION MANUAL Firmware Version 1 1 Franklin Electric Co Inc ...
Страница 94: ...COMMUNICATIONS BACnet Communication 94 ...
Страница 98: ...ACCESSORIES Optional Extension Cards 98 Frame D Frame E Frame F ...
Страница 99: ...ACCESSORIES Optional Extension Cards 99 Frame G Frame H ...
Страница 102: ...ACCESSORIES Optional Extension Cards 102 ...