PARAMETER REFERENCE TABLES
Parameter Descriptions > COMM Menu
132
Parameter Descriptions > COMM Menu
AR = Adjustable while running.
PROT-45 1069 Y Fan Control
0_At Power-Up
1_Delayed Stop
2_During Run
3_By Temperature
4_Disabled
Determines operation of fan. Recommend not to set to 4-Disabled since
this will reduce performance of drive.
PROT-46 1070 Y Last Flt Freq
0.0 to SET-14 Hz
Output frequency at last fault (Read Only)
PROT-47 1071 Y Last Flt IGBTT
-3277 to 3276.7 °C
IGBT temperature at last fault (Read Only)
PROT-48 1072 Y Last Flt Cap T
-3277 to 3276.7 °C
Capacitance temperature at last fault (Read Only)
PROT-49 1073 Y Last Flt MFI
(Read Only)
Status of Multi-function input terminals at last fault
PROT-50 1074 Y Last Flt MFO
(Read Only)
Status of Multi-function output terminals at last fault
PROT-51 1075 Y 1st Fault
(Read Only)
First register of fault listing.
PROT-52 1076 Y 2nd Fault
(Read Only)
Second register of fault listing.
PROT-53 1077 Y 3rd Fault
(Read Only)
Third register of fault listing.
PROT-54 1078 Y 4th Fault
(Read Only)
Fourth register of fault listing.
PROT-55 1079 Y 5th Fault
(Read Only)
Fifth register of fault listing.
PROT-56 1080 Y 6th Fault
(Read Only)
Sixth register of fault listing.
PROT-57 1081 Y ULD Min Torque 5% to SET-42
Sets minimum torque level % at 0Hz when using Underload Torque.
PROT-58 1082 Y HLD Min Torque PROT-57 to SET-48
Sets minimum torque level % at 0Hz when using High load Torque.
CODE
Mod
Bus AR Display Name
Range
Description
CODE
Mod
Bus AR Display Name
Range
Description
Comm-00 1280 Y COM1 Address
1 to 254
RS485 address of VFD.
Comm-01 1281 Y COM1 Speed
4.8 to 115.2 Kbps
RS485 baud rate. All devices on RS485 communication must have the
same baud rate.
Comm-02 1282 Y COM1 Loss
0_Alarm and Run
1_Alarm_Decel
2_Alarm_Coast
3_Disable
Select operation when communication is lost.
Comm-03 1283 Y COM1 Loss Delay 0.0 to 100 Sec
Duration of communication loss before initiating operation.
Comm-04 1284 Y COM1 Protocol
1_7, N, 2 for ASCII
2_7, E, 1 for ASCII
3_7, O, 1 for ASCII
4_7, E, 2 for ASCII
5_7, O, 2 for ASCII
6_8, N, 1 for ASCII
7_8, N, 2 for ASCII
8_8, E, 1 for ASCII
9_8, O, 1 for ASCII
10_8, E, 2 for ASCII
11_8, O, 2 for ASCII
12_8, N, 1 for RTU
13_8, N, 2 for RTU
14_8, E, 1 for RTU
15_8, O, 1 for RTU
16_8, E, 2 for RTU
17_8, O, 2 for RTU
RS485 Protocol: Data Bits - Parity - Stop Bits - Message Format
Comm-05 1285 Y Response Delay 0.0 to 200 ms
Duration VFD waits before responding to received communication.
Comm-06 1286 N Main Frequency 0.0 to 599 Hz
When Auto Speed Ref [SET-07] is set to RS485 Interface, the last fre
-
quency command is stored in this parameter. After rebooting from an
abnormal turn-off or momentary power loss, the VFD will continue opera
-
tion with last frequency.
Содержание Cerus X-Drive
Страница 1: ...franklin electric com ENGLISH EN CERUSX DRIVE Installation and Operation Manual Firmware Version 1 1 ...
Страница 2: ......
Страница 3: ...CERUS X DRIVE INSTALLATION AND OPERATION MANUAL Firmware Version 1 1 Franklin Electric Co Inc ...
Страница 94: ...COMMUNICATIONS BACnet Communication 94 ...
Страница 98: ...ACCESSORIES Optional Extension Cards 98 Frame D Frame E Frame F ...
Страница 99: ...ACCESSORIES Optional Extension Cards 99 Frame G Frame H ...
Страница 102: ...ACCESSORIES Optional Extension Cards 102 ...