PARAMETER REFERENCE TABLES
Parameter Descriptions > SET Menu
115
PARAMETER REFERENCE TABLES
Parameter Descriptions > SET Menu
AR = Adjustable while Running.
CODE Mod
Bus AR Display Name
Range
Description
SET-00 0000 N Application Sel
0_Basic
1_Supply Fan
2_Exhaust Fan
3_Cooling Tower
4_Centrifugal Pump
5_Submersible Pump
6_Vacuum Pump
7_Constant Torque Motor
8_PM Motor
9_MagForce
Mechanical application the VFD is running. Must be set when powered up
the first time. Selection automatically adjusts many default parameters to
common values for the application. Additional adjustments may be
required for optimum performance.
Refer to the application descriptions in
“Standard Operation with an Auto
mated Control System” on page 66
for more information.
Important:
Whenever the application is changed, many default parame
-
ters are changed. Be sure to verify settings to ensure proper operation.
Refer to the Default Settings tables in
“Default Settings Tables” on page 50
SET-01 0001 N Input Phase
0_Three-Phase
1_Single-Phase
The VFD is capable of using a 3-Phase or Single-Phase input power source,
but should be derated for Single-Phase input power.
SET-02 0002 N Motor HP
0.5~655 HP
Default is set based on VFD rating.
User should enter the rated motor HP, found on the motor nameplate.
SET-03 0003 N Motor FLA/SFA
1/10 of max capacity~999.9A Default is set based on VFD rating.
User should enter the rated motor FLA, found on the motor nameplate. If
[SET-00] is set to Submersible, enter the SFA rating from the motor name
-
plate.
All internal overload protection features for the VFD and motor are calcu
-
lated based on the value in this parameter.
SET-04 0004 N Motor RPM
0-3600 RPM
Rated Motor RPM from motor nameplate when running at nameplate fre
-
quency.
SET-05 0005 N Motor Voltage
230V: 0 to 255 V
460V: 0 to 510 V
575V: 0 to 637 V
690V: 0 to 720 V
Rated voltage of the motor, found on the motor nameplate. The VFD can
produce output voltage equal to or less than input power voltage.
SET-06 0006 Y Carrier Freq
2.0 to 15.0 kHz
Varies by VFD rating
VFD switching frequency. Higher frequencies create more precise wave
forms, but generate higher heat. Lower frequencies run cooler, but could
potentially cause audible noise, which can be eliminated by adjusting this
carrier frequency during stop or run mode
.
SET-07 0007 N Auto Speed Ref
0_Keypad
1_Up/Down DI
2_AVI1 Analog Input
3_ACI Analog Input
4_AVI2 Analog
5_RS485 Serial
6_Com Card
7_PID Output
Source of speed reference when in Auto mode.
Keypad input.
Digital Input when DI terminal [IO-21~28] set to Up and Down.
Analog input from BMS, PLC, Potentiometer or other control device.
RS-485 Interface
Communications card control.
PID output. When PID mode is selected, additional parameters must be
verified for setpoints, inputs, and limits.
SET-08 0008 N Auto Run Cmd
0_Keypad
1_Digital Input
2_RS485 Serial
3_Com Card
4_Ext HOA in Auto
Source of Run Command in Auto mode.
Keypad: Run command from Start/Stop button.
Digital Input: Run command from digital input FWD or REV terminal. Key
-
pad STOP is disabled.
RS485 Serial: Run command from RS485 interface. Keypad STOP is dis
-
abled.
Com Card: Run command from communications card. This does not include
CANopen card.
Ext HOA in Auto: Run command from digital input [IO-21~28] set to HOA
AUTO (when HOA is in Auto position).
Содержание Cerus X-Drive
Страница 1: ...franklin electric com ENGLISH EN CERUSX DRIVE Installation and Operation Manual Firmware Version 1 1 ...
Страница 2: ......
Страница 3: ...CERUS X DRIVE INSTALLATION AND OPERATION MANUAL Firmware Version 1 1 Franklin Electric Co Inc ...
Страница 94: ...COMMUNICATIONS BACnet Communication 94 ...
Страница 98: ...ACCESSORIES Optional Extension Cards 98 Frame D Frame E Frame F ...
Страница 99: ...ACCESSORIES Optional Extension Cards 99 Frame G Frame H ...
Страница 102: ...ACCESSORIES Optional Extension Cards 102 ...