PHYSICAL INSTALLATION
Conduit Box Installation
22
Conduit Box Installation
Frames A, B and C do not require an added conduit box.
Frames D0 and D Conduit Box Installation
1.
Loosen two lower drive cover screws.
2. Press the tabs on each side of the cover.
3. Remove the cover.
4. Remove five screws.
5. Install the conduit box with five screws. Tighten to a torque of
24-26 kg-cm / 20.8-22.6 Ib-in. / 2.4-2.5 Nm.
6. Replace the lower drive cover and rotate to the closed position.
Secure with two screws from step 1. Tighten to a torque of
12-15 kg-cm / 10.4-13 Ib-in. / 1.2-1.5 Nm.