PARAMETER REFERENCE TABLES
Parameter Descriptions > SET Menu
201
PARAMETER REFERENCE TABLES
Parameter Descriptions > SET Menu
AR = Adjustable while Running.
CODE Mod
Bus AR Display Name
Range
Description
SET-00 0000 N Application Sel
0_Basic
1_Supply Fan
2_Exhaust Fan
3_Cooling Tower
4_Centrif Pump
5_Submers Pump
6_Vacuum
7_Constant Torque
8_FE MagForce
9_PM Motor
Mechanical application the VFD is running; should be set first during VFD
programming. Selection automatically adjusts many default parameters to
common values for the application. Additional adjustments may be
required for optimum performance.
Refer to the application descriptions in
for more
information.
IMPORTANT:
Whenever the application is changed, many default parame
-
ters are changed. Be sure to verify settings to ensure proper operation.
Refer to the Default Settings tables in
“Default Settings Table - SET Menu”
.
SET-01 0001 N Input Phase
0_Three-Phase
1_Single-Phase
The VFD is capable of using a 3-Phase or Single-Phase input power source,
but should be de-rated for Single-Phase input power.
SET-02 0002 N Motor HP
0.5~655 HP
Default is set based on VFD rating.
User should enter the rated motor HP, found on the motor nameplate.
SET-03 0003 N Motor FLA (SFA) 1/10 of max capacity~999.9
Full Load Amperage
Default is set based on VFD rating.
User should enter the rated motor FLA, found on the motor nameplate. If
[SET-00]
is set to
5_Submersible
, enter the SFA rating from the motor name
-
plate.
All internal overload protection features for the VFD and motor are calcu
-
lated based on the value in this parameter.
SET-04 0004 N Motor RPM
0-3600 RPM
Rated Motor RPM from motor nameplate when running at nameplate fre
-
quency.
SET-05 0005 N Motor Voltage
230V: 0 to 255 V
460V: 0 to 510 V
575V: 0 to 637 V
690V: 0 to 720 V
Rated voltage of the motor, found on the motor nameplate. The VFD can
produce output voltage equal to or less than input power voltage.
SET-06 0006 N Motor Freq Sel
0_50Hz
1_60Hz
Motor rated frequency. If
Motor Freq Sel [SET-06]
is changed to 50 Hz, all output
frequency related parameters are adjusted. Refer to
- Frequency Defaults with 50 Hz” on page 62
SET-07 0007 N Auto Speed Ref
0_Keypad
1_Up/Down DI
2_AVI1 Analog
3_ACI Analog
4_AVI2 Analog
5_RS485 Serial
6_Com Card
7_PID Output
Source of speed reference when in Auto mode.
0_Keypad input.
1_Digital Input when DI terminal
[IO-21]
to
[IO-28]
set to
Up
and
Down
.
2, 3, & 4_Analog input from BMS, PLC, Potentiometer or other control
device.
5_RS-485 Interface
6_Communications card control.
7_PID output. When PID mode is selected, additional parameters must be
verified for setpoints, inputs, and limits.
SET-08 0008 N Auto Run Cmd
0_Keypad
1_Digital Input
2_RS485 Serial
3_Com Card
4_Ext HOA in Auto
Source of Run Command in Auto mode.
0_Keypad: Run command from Start/Stop button.
1_Digital Input: Run command from digital input
[IO-21]
to
[IO-28]
set to
38_FWD
or
39_REV
. If direction is set here, then dedicated FWD input is dis
-
abled. Keypad STOP is disabled.
2_RS485 Serial: Run command from RS485 interface. Keypad STOP is dis
-
abled.
3_Com Card: Run command from communications card. This does not
include CANopen card.
4_External HOA in Automatic: Run command from digital input
[IO-21]
to
[IO-28]
set to
27_HOA-AUTO
(when HOA is in Auto position).
Содержание CERUS X-DRIVE CXD-003A-4V
Страница 1: ...franklin electric com ENGLISH EN CERUSX DRIVE Installation and Operation Manual Firmware Version 1 2 ...
Страница 2: ......
Страница 3: ...CERUS X DRIVE INSTALLATION AND OPERATION MANUAL Firmware Version 1 2 Franklin Electric Co Inc ...
Страница 96: ...OPERATION Protection Features 96 ...
Страница 112: ...ADVANCED APPLICATION OPTIONS Multi Drive Configurations 112 ...
Страница 124: ...COMMUNICATIONS BACnet Communication 124 ...
Страница 128: ...ACCESSORIES Optional Extension Cards 128 Frame D Frame E Frame F ...
Страница 129: ...ACCESSORIES Optional Extension Cards 129 Frame G Frame H ...
Страница 132: ...ACCESSORIES Optional Extension Cards 132 ...
Страница 234: ...PARAMETER REFERENCE TABLES Parameter Descriptions Motor Menu 234 ...
Страница 250: ...GLOSSARY 250 ...
Страница 252: ...For technical assistance parts or repair please contact 800 348 2420 franklin electric com 10000005064 Rev 004 09 22 ...