FRANCO s.r.l.                                                                                               User and maintenance manual ROOF COOLER 

 

 

1.7 Applications 

 
The  ROOF  COOLER  is  an  evaporative  cooler  for  large  rooms,  such  as  workshops,  industrial 
departments,  commercial  and  civil  buildings,  agricultural  and  livestock  premises,  etc.,  which  works 
based on the principle of adiabatic cooling. Warm air is drawn in from outside, flows across the high-
efficiency evaporative panels and comes into contact with the water flowing through the panels from top 
to bottom. The evaporation removes heat from the air and naturally lowers its temperature. The fresh 
air  is  then  conveyed  and  distributed  to  the  space  to  be  cooled  through  a  duct.  The  cooling  capacity 
depends on the temperature, room humidity and air distribution.  
As well as a cooler, the unit can also be used as a humidifier for large room volumes, in industrial, civil, 
agricultural and livestock applications, or as a simple ventilator, when cooling or humidification is not 
necessary.  
The materials used guarantee reliability and durability, even in the most critical environments. 

 

 

This machine must only be used for the purpose 
for  which  it  was  designed:  "Adiabatic  cooling/humidification".  All 
other  uses  are  considered  improper  and  therefore  potentially 
dangerous

 

 

1.8 Versions

 

 

The ROOF COOLER evaporative cooler is available in the following versions: 

 

 

BOTTOM 

TOP 

SIDE 

 

 

 

 
 
 

Version 

Article number 

Power supply 

Motor 

Bottom 
(air exit 
from below) 
 

without fan* 

2903100 

230V 50Hz 

with fan 

2903000 

400V 3N~ 50Hz 

fixed speed 

2903001 

400V 3N~ 50Hz 

variable speed 

2903005 

230V 50Hz 

variable speed 

Top 
(air exit from 
above) 
 

without fan* 

2903011 

230V 50Hz 

with fan 

2903010 

400V 3N~ 50Hz 

fixed speed 

2903013 

400V 3N~ 50Hz 

variable speed 

2903012 

230V 50Hz 

variable speed 

Side 
(air exit on  
one side) 
 

without fan* 

2903021 

230V 50Hz 

with fan 

2903020 

400V 3N~ 50Hz 

fixed speed 

2903022 

400V 3N~ 50Hz 

variable speed 

2903024 

230V 50Hz 

variable speed 

*Versions without fan must be integrated in a dynamic ventilation system with a maximum air flow of 
15000 m³/h.  

Содержание 20903012

Страница 1: ...ATIVE COOLER T R A N S L AT I O N O F O R I G I N A L I N S T R U C T I O N S E N G L I S H C O U N T R Y O F D E S T I N AT I O N G B Read this manual carefully before installing and using the machin...

Страница 2: ...ufacturer s identification data 9 1 14 Declarations 9 1 15 Declaration of conformity 10 1 16 Declaration of incorporation 11 2 INSTALLATION 12 2 1 Getting started 12 2 2 Positioning 12 2 3 Electrical...

Страница 3: ...or physically or mentally unfit persons from using the device without proper supervision Do not touch the cooler during operation Never immerse the appliance in water or any other liquid or hit it wit...

Страница 4: ...the manufacturer s responsibility to send the customer the parts affected by the modification The user must replace the old parts with the new parts in the manual he has The manufacturer is responsibl...

Страница 5: ...or qualified to use lifting and handling equipment and machines strictly following the manufacturer s instructions in accordance with the laws in force in the country of the machine user Mechanical ma...

Страница 6: ...rsonal injury or property damage for which the manufacturer cannot be held responsible All technical legislative and accident prevention regulations in force in the country of destination must also be...

Страница 7: ...ator when cooling or humidification is not necessary The materials used guarantee reliability and durability even in the most critical environments This machine must only be used for the purpose for w...

Страница 8: ...echnical reference data are indelibly marked Always quote these references in any communication with the manufacturer or service centres Fig 1 9 1 Fig 1 9 1 1 10 Description of equipment Main componen...

Страница 9: ...om the date of manufacture for all faults attributable to a proven manufacturing or material defect The warranty does not cover all parts damaged by transport bad or incorrect maintenance neglect inab...

Страница 10: ...g Humidification Intended use complies with the following European Directives 2006 42 EC Machinery Directive 2014 35 EU Low Voltage Directive 2014 30 EU Electromagnetic Compatibility Directive Harmoni...

Страница 11: ...6 42 C complies with the following EU directives Directive 2006 95 EC Directive 2004 108 EC The relevant technical documentation has been prepared in accordance with Annex VII B Dir 2006 42 EC The man...

Страница 12: ...me air extractors can be installed so that the extracted air flow rate is at least 80 of the air flow rate introduced into the room by the cooler s The efficiency of the process and therefore the room...

Страница 13: ...ig 2 2 3 TOP air outlet from above WALL installation Fig 2 2 4 SIDE side air outlet WALL installation Further information regarding installation procedures system sizing available accessories etc are...

Страница 14: ...y with the information on the dataplate It is mandatory to connect the appliance to an efficient earthing line The installation must include an omnipolar disconnection device for the appliance from th...

Страница 15: ...sure that all hydraulic connections have been made correctly Open the water supply tap and check that there are no leaks along the supply circuit Check the operation of the float valve and adjust the...

Страница 16: ...for recirculating water ALGAE PREVENTION To avoid algae formation carry out regular drying cycles of the panels stop the water recirculation pump and leave the fan running for a few minutes to allow t...

Страница 17: ...ways completely wet during operation d At the end of the working season Disconnect the unit from the power and water supply at the end of the summer season or if the unit is not used for a long period...

Страница 18: ...3 Remove the side grills Periodically check and clean the water distributors with a soft brush For more thorough cleaning disconnect the distributors from the top cover by unscrewing the fixing screw...

Страница 19: ...e label near the float For replacement disconnect the water supply and remove any fittings from the machine connection Unscrew the plastic ring nut and remove the float body Position the new float and...

Страница 20: ...Maximum air flow rate m h 15000 15000 15000 Dry weight kg 70 70 55 Tank capacity l 45 45 45 Delivery channel connection mm square 660x660 round 610 Pressure drop Pa 100 FAN Power supply 400V 3 50Hz 2...

Страница 21: ...d comply with current regulations The power supply cables must be replaced by the manufacturer his technical service or a qualified person in order to prevent any risk The machine is equipped with thr...

Страница 22: ...R At the bottom of the water collection tank there is a level sensor Reed contact with the following characteristics Maximum switching voltage 100 V DC Maximum switching current 0 5 A Interfacing the...

Страница 23: ...nd maintenance manual ROOF COOLER 23 5 4 Spare parts list Use only original spare parts When ordering spare parts always specify the following Model and serial number Part number Quantity Shipping add...

Страница 24: ...FRANCO s r l User and maintenance manual ROOF COOLER 24 TOP VERSION SIDE VERSION...

Страница 25: ...shead screw for fixing posts 9 2901050 8 Panel locking band 9 1 6001605 32 Phillips pan head screw 4 2x16 for fixing panel strips 10 2901040 4 3 Evaporative panel 11 2901190 8 6 Air inlet filter 12 29...

Страница 26: ...pump supply voltage Check the pump supply line Water supply circuit disconnected Check the water supply line Water distribution circuit disconnected or clogged Check the pipes hoses of the water dist...

Страница 27: ...leaking from the collection tank Float water level not correctly adjusted Check and adjust the water level Excessive water flow rate supply pressure Check and adjust the water supply Exhaust valve def...

Страница 28: ...ce manual ROOF COOLER 28 FRANCO s r l Head office and factory Via Nazionale n 80 12010 CERVASCA CUNEO Italy Tel 39 0171 611663 www francosrl com info francosrl com For reports or requests please conta...