background image

FRANCO s.r.l.                                                                                               User and maintenance manual ROOF COOLER 

 

 

1 - INTRODUCTION 

 

1.1 General safety instructions 

 
This  appliance  must  only  be  used  for  the  function  for  which  it  was  designed  "Adiabatic  cooler  / 
humidifier". Any other use is to be considered improper and dangerous. Franco s. r. l. cannot be held 
responsible  for  any  damage  resulting  from  improper,  incorrect  and  unreasonable  use,  such  as,  for 
example: 
 

installation errors  

incorrect power or water supply 

unauthorised mechanical or electrical modifications 

removal of guards or safety devices  

lack of maintenance 

use of non-original spare parts 

non-compliance with the operating and maintenance instructions 

 
- When opening the packaging, check that the appliance is intact and does not show any damage or 
deformation of the plastic parts. If this is the case, do not install the appliance and contact the service 
department.  
 
- Before connecting the appliance, make sure that the data on the rating plate (voltage, frequency, etc.) 
correspond to those on the mains. The technical data label is located on the bottom side of the appliance 
(see par. 1.9). 
 
- Comply with the safety rules indicated for electrical equipment, and in particular:  

  Follow the operating and maintenance instructions for the appliance. 

  Do not place objects on the cooler. 

  Prevent children and/or physically or mentally unfit persons from using the device without proper 

supervision; 

  Do not touch the cooler during operation. 

  Never immerse the appliance in water or any other liquid, or hit it with pressurised water.  

  Do not place any objects inside the appliance.  

  Do  not  use  accessories,  spare  parts  and  components  not  intended  for  or  supplied  by  the 

manufacturer. 

  Avoid touching the device with wet or damp hands. 

  Do not pull power cables or expose them to risk of shearing. 

  In the event of a fault or malfunction, switch off the appliance immediately and disconnect the 

power supply. Do not attempt to open or tamper with the appliance: contact the technical service. 

  Do not attempt to fill or empty the drip tank manually when the appliance is in operation. 

  Do not remove the guards during use. 

  Do not install the device in explosion hazard areas. 

 

1.2 Warnings for the correct disposal of the product (EU) 

 
Pursuant to European Directive 2012/19/EU: 
At the end of its useful life, the appliance must be delivered to the appropriate separate 
waste  collection  points  set  up  by  the  local  authorities,  or  to  retailers  who  provide  this 
service. Disposing of the product separately avoids possible negative consequences for 
the  environment  and  health,  and  allows  the  materials  from  which  it  is  made  to  be 
recovered, thus saving energy and resources. To emphasise the obligation to dispose of 
electrical and electronic equipment separately, the product is marked with a crossed-out 
wheeled bin. 

 
 
           Fig. 1.2.1 

Содержание 20903012

Страница 1: ...ATIVE COOLER T R A N S L AT I O N O F O R I G I N A L I N S T R U C T I O N S E N G L I S H C O U N T R Y O F D E S T I N AT I O N G B Read this manual carefully before installing and using the machin...

Страница 2: ...ufacturer s identification data 9 1 14 Declarations 9 1 15 Declaration of conformity 10 1 16 Declaration of incorporation 11 2 INSTALLATION 12 2 1 Getting started 12 2 2 Positioning 12 2 3 Electrical...

Страница 3: ...or physically or mentally unfit persons from using the device without proper supervision Do not touch the cooler during operation Never immerse the appliance in water or any other liquid or hit it wit...

Страница 4: ...the manufacturer s responsibility to send the customer the parts affected by the modification The user must replace the old parts with the new parts in the manual he has The manufacturer is responsibl...

Страница 5: ...or qualified to use lifting and handling equipment and machines strictly following the manufacturer s instructions in accordance with the laws in force in the country of the machine user Mechanical ma...

Страница 6: ...rsonal injury or property damage for which the manufacturer cannot be held responsible All technical legislative and accident prevention regulations in force in the country of destination must also be...

Страница 7: ...ator when cooling or humidification is not necessary The materials used guarantee reliability and durability even in the most critical environments This machine must only be used for the purpose for w...

Страница 8: ...echnical reference data are indelibly marked Always quote these references in any communication with the manufacturer or service centres Fig 1 9 1 Fig 1 9 1 1 10 Description of equipment Main componen...

Страница 9: ...om the date of manufacture for all faults attributable to a proven manufacturing or material defect The warranty does not cover all parts damaged by transport bad or incorrect maintenance neglect inab...

Страница 10: ...g Humidification Intended use complies with the following European Directives 2006 42 EC Machinery Directive 2014 35 EU Low Voltage Directive 2014 30 EU Electromagnetic Compatibility Directive Harmoni...

Страница 11: ...6 42 C complies with the following EU directives Directive 2006 95 EC Directive 2004 108 EC The relevant technical documentation has been prepared in accordance with Annex VII B Dir 2006 42 EC The man...

Страница 12: ...me air extractors can be installed so that the extracted air flow rate is at least 80 of the air flow rate introduced into the room by the cooler s The efficiency of the process and therefore the room...

Страница 13: ...ig 2 2 3 TOP air outlet from above WALL installation Fig 2 2 4 SIDE side air outlet WALL installation Further information regarding installation procedures system sizing available accessories etc are...

Страница 14: ...y with the information on the dataplate It is mandatory to connect the appliance to an efficient earthing line The installation must include an omnipolar disconnection device for the appliance from th...

Страница 15: ...sure that all hydraulic connections have been made correctly Open the water supply tap and check that there are no leaks along the supply circuit Check the operation of the float valve and adjust the...

Страница 16: ...for recirculating water ALGAE PREVENTION To avoid algae formation carry out regular drying cycles of the panels stop the water recirculation pump and leave the fan running for a few minutes to allow t...

Страница 17: ...ways completely wet during operation d At the end of the working season Disconnect the unit from the power and water supply at the end of the summer season or if the unit is not used for a long period...

Страница 18: ...3 Remove the side grills Periodically check and clean the water distributors with a soft brush For more thorough cleaning disconnect the distributors from the top cover by unscrewing the fixing screw...

Страница 19: ...e label near the float For replacement disconnect the water supply and remove any fittings from the machine connection Unscrew the plastic ring nut and remove the float body Position the new float and...

Страница 20: ...Maximum air flow rate m h 15000 15000 15000 Dry weight kg 70 70 55 Tank capacity l 45 45 45 Delivery channel connection mm square 660x660 round 610 Pressure drop Pa 100 FAN Power supply 400V 3 50Hz 2...

Страница 21: ...d comply with current regulations The power supply cables must be replaced by the manufacturer his technical service or a qualified person in order to prevent any risk The machine is equipped with thr...

Страница 22: ...R At the bottom of the water collection tank there is a level sensor Reed contact with the following characteristics Maximum switching voltage 100 V DC Maximum switching current 0 5 A Interfacing the...

Страница 23: ...nd maintenance manual ROOF COOLER 23 5 4 Spare parts list Use only original spare parts When ordering spare parts always specify the following Model and serial number Part number Quantity Shipping add...

Страница 24: ...FRANCO s r l User and maintenance manual ROOF COOLER 24 TOP VERSION SIDE VERSION...

Страница 25: ...shead screw for fixing posts 9 2901050 8 Panel locking band 9 1 6001605 32 Phillips pan head screw 4 2x16 for fixing panel strips 10 2901040 4 3 Evaporative panel 11 2901190 8 6 Air inlet filter 12 29...

Страница 26: ...pump supply voltage Check the pump supply line Water supply circuit disconnected Check the water supply line Water distribution circuit disconnected or clogged Check the pipes hoses of the water dist...

Страница 27: ...leaking from the collection tank Float water level not correctly adjusted Check and adjust the water level Excessive water flow rate supply pressure Check and adjust the water supply Exhaust valve def...

Страница 28: ...ce manual ROOF COOLER 28 FRANCO s r l Head office and factory Via Nazionale n 80 12010 CERVASCA CUNEO Italy Tel 39 0171 611663 www francosrl com info francosrl com For reports or requests please conta...