Interface

Setting

DIS:

 Disables the runtime limit timer, in which case backup

 

time will depend on battery capacity. (Default)

Note: 

When setting this parameter to “0”, the backup time

will only last 10 seconds. 

Use this setting to configure the backup time on battery 
mode for general outlets. 

0-999: 

 Sets the backup time in minutes, from 0-999 for 

general outlets on battery mode.

Interface

Setting

 

HS:

 Bypass high frequency point

For 50Hz output frequency models: 
51-55Hz: Sets the frequency high loss point from 51Hz to

 

55HZ (Default: 53.0Hz)
For 60Hz output frequency models: 
61-65Hz: Sets the frequency high loss point from 61Hz to
65Hz (Default: 63.0Hz)

LS: 

Bypass low frequency point

For 50Hz output frequency models: 
45-49Hz: Sets the frequency low loss point from 45Hz to

 

49HZ (Default: 47.0Hz)
For 60Hz output frequency models: 
55-59Hz: Sets the frequency low loss point from 55Hz to

 

59Hz (Default: 57.0Hz)

Use this menu to set the acceptable high frequency point 
and acceptable low frequency point for Bypass mode by 
pressing the 

Down

 key or 

Up

 key.

09: Bypass frequency range setting

11: Backup time setting for programmable outlets

Interface

Setting

Parameter 3

:

 

Sets the backup time limits for the 

programmable outlets.

0-999

: Use this setting to define the programmable outlets 

backup time in minutes, from 0-999, in order to connect 
non-critical devices on battery mode. (Default:999)

10: Programmable outlets enable/disable

Interface

Setting

Parameter 3

:

 

Activates or cancels the programmable 

outlet feature.

ENA

: Programmable outlets enabled

DIS

: Programmable outlets disabled (Default)

Interface

Setting

Use this setting to configure the charger current to be applied. 
When the UPS is equipped with an additional charge, the

r

available setting options are 2/3/4. 

2/3/4: 

Sets the maximum charger current in 2/3/4 amperes.

 

 

Long-run models have settings  of 1/2/4/6/8. available. 

.

1/2/4/6/8:

 Sets the maximum charger current in 1/2/4/6/8

 

amperes. (Default: 8A) 

Interface

Use this setting to  configure  the boost voltage level.

225-240: 

Sets the charger boost voltage from 225 to

 

240 (unit: 0.01V/cell). (Default: 236) 

12: Backup time setting for general outlets

13: Battery total Ah setting

14: Maximum charger current setting

15: Charger boost voltage setting

Interface

Setting

Use this setting to configure the total battery capacity in 
Ah for the UPS sytem. 

7-999: 

 Sets the battery total capacity from 7-999 in Ah.

Please set the correct battery total capacity if an external
battery bank is connected.

Содержание FDC-1502R

Страница 1: ...2 Y e a r w a r r a n t y...

Страница 2: ...k Do not install the UPS system near water or in moist environments Do not install the UPS system where it would be exposed to direct sunlight or near a heater or heating vent Do not block ventilation...

Страница 3: ...y can result in electrical shock The likelihood of such shock can be reduced if such grounds are removed during installation and maintenance When replacing the battery make sure to use the same type a...

Страница 4: ...S it will provide advanced communication and monitoring options Note The USB port and RS 232 port cannot be used at the same time CAUTION For 1 5K model to reduce the risk of re connect only to a circ...

Страница 5: ...n the same LAN no matter how far they might be from the UPS 2 6 Battery replacement Service personnel only NOTICE This UPS is equipped with internal batteries and only quali ed service personnel shall...

Страница 6: ...r display Load information UPS status Battery information Display Function Backup time information Overload indicator Indicates the load or the UPS output is short circuited Indicates that the program...

Страница 7: ...Two parameters need to be configured in order to set up the UPS Refer to following diagram Parameter 1 it is used for the different configuration options Please refer to the table below Parameter 2 it...

Страница 8: ...3 is from 7V to 24V of the nominal voltage Default 12V For 100 110 115 120 127 VAC models the setting voltage in parameter 3 is from 3V to 12V of the nominal voltage Default 6V 08 Bypass voltage range...

Страница 9: ...tting Parameter 3 Sets the backup time limits for the programmable outlets 0 999 Use this setting to define the programmable outlets backup time in minutes from 0 999 in order to connect non critical...

Страница 10: ...t voltage is within the voltage regulation range 3 V max the UPS will bypass voltage to loads for energy saving PFC and INVERTER are disabled in this mode When input frequency is between 40Hz and 70Hz...

Страница 11: ...s connected to the UPS outlet The AC input cable is not properly connected Line and neutral conductors of UPS input are reversed The external or internal battery connection is incorrect Battery voltag...

Страница 12: ...S system contains no user serviceable parts If the battery service life 3 5 years at 25 C ambient temperature has been exceeded the batteries must be replaced In this case please contact your dealer o...

Отзывы: