Interface
Setting
DIS:
Disables the runtime limit timer, in which case backup
time will depend on battery capacity. (Default)
Note:
When setting this parameter to “0”, the backup time
will only last 10 seconds.
Use this setting to configure the backup time on battery
mode for general outlets.
0-999:
Sets the backup time in minutes, from 0-999 for
general outlets on battery mode.
Interface
Setting
HS:
Bypass high frequency point
For 50Hz output frequency models:
51-55Hz: Sets the frequency high loss point from 51Hz to
55HZ (Default: 53.0Hz)
For 60Hz output frequency models:
61-65Hz: Sets the frequency high loss point from 61Hz to
65Hz (Default: 63.0Hz)
LS:
Bypass low frequency point
For 50Hz output frequency models:
45-49Hz: Sets the frequency low loss point from 45Hz to
49HZ (Default: 47.0Hz)
For 60Hz output frequency models:
55-59Hz: Sets the frequency low loss point from 55Hz to
59Hz (Default: 57.0Hz)
Use this menu to set the acceptable high frequency point
and acceptable low frequency point for Bypass mode by
pressing the
Down
key or
Up
key.
09: Bypass frequency range setting
11: Backup time setting for programmable outlets
Interface
Setting
Parameter 3
:
Sets the backup time limits for the
programmable outlets.
0-999
: Use this setting to define the programmable outlets
backup time in minutes, from 0-999, in order to connect
non-critical devices on battery mode. (Default:999)
10: Programmable outlets enable/disable
Interface
Setting
Parameter 3
:
Activates or cancels the programmable
outlet feature.
ENA
: Programmable outlets enabled
DIS
: Programmable outlets disabled (Default)
Interface
Setting
Use this setting to configure the charger current to be applied.
When the UPS is equipped with an additional charge, the
r
available setting options are 2/3/4.
2/3/4:
Sets the maximum charger current in 2/3/4 amperes.
Long-run models have settings of 1/2/4/6/8. available.
.
1/2/4/6/8:
Sets the maximum charger current in 1/2/4/6/8
amperes. (Default: 8A)
Interface
Use this setting to configure the boost voltage level.
225-240:
Sets the charger boost voltage from 225 to
240 (unit: 0.01V/cell). (Default: 236)
12: Backup time setting for general outlets
13: Battery total Ah setting
14: Maximum charger current setting
15: Charger boost voltage setting
Interface
Setting
Use this setting to configure the total battery capacity in
Ah for the UPS sytem.
7-999:
Sets the battery total capacity from 7-999 in Ah.
Please set the correct battery total capacity if an external
battery bank is connected.