The purpose of this section is to ensure that the IDDX Flame Amplifier is properly setup and configured,
using recommended Forney practices.
The amplifier tuning mode can be reached using either the handheld Termiflex/SmartDisplay® or the
Forney Terminal Emulator Software (TES) installed on a laptop computer. Table 3-1 Keypad Commands
summarizes the keypad commands available in the IDDX Flame Amplifier firmware program.
The three key sequence “/13” (slash, one, three) is pressed to enter the tuning loop. The amplifier is tuned
in the active mode only.
Note:
•
During tuning, any changes that cause loss of flame indication will be transmitted to the main flame
relay following the FFRT delay.
•
While tuning, if the main flame relay drops, the system will not re-initiate Flame-on status until the
user exits the tuning loop. If the flame lamp indicator is on when the tuning loop is exited, the system
will then return to flame-on status.
SECTION 3
SETUP AND CONFIGURATION
12
372001-24 Rev. A
IDDX Flame Detector Amplifier Manual
Table 3-1 Keypad Commands
Function
Termiflex / SmartDisplay®
Key strokes
Terminal Emulator Software
(TES) Button
Enter the tuning loop
/ 1 3
Slash one three
Config
Do self-check now
?
Question mark
Self Test