TECHNICAL DATA
1.3
Electrical
Mechanical
Power Supply:
24 VDC (+/-10%)
Steady State Current:
265 mA
Inrush Current:
1 A
Power Consumption:
6.5 Watt
External In-line Fuse:(Required)1
1A Fuse (Customer Furnished)
Terminal Size:
18 AWG
Heat Dissipation:
4 Watt
Flame Relay:
1 (fail safe)
Contacts: (External 500 mA Fuse
Required in series)
SPST, 250VAC/5A
Conformal Coating:
No
Relay Operating Cycle:
> Min 20 X 106 Operations
Flame Failure Response Time
(FFRT):
1, 2, 3, 3.8 second (user adjustable)
Fault Relay:
1
Analog Output:
One Sourced 4-20 mA, Load resistance <= 500 Ohm
Profile Selection Digital Inputs:
2 Self-Powered Inputs
Communication (Wired):
RS-422 (Termiflex)
Housing Material:
Engineered Polymer
Weight:
0.62 lbs. (280 gms.)
Degree of Protection:
IP20, NEMA 1
7
372001-24 Rev. A
IDDX Flame Detector Amplifier Manual