37
PLC Register:
Function code 03
Modbus address
Function description
instruction
Hex
Decimal
0x3000
12290
Read current TEI
0-99
0x3001
12290
Read the number of packets
currently sent
0x3002
12290
Read the current working mode
1: gateway mode, 0: node mode
0x3003
12291
Read the number of nodes online The value range is 0 ~ 16, the current number of online nodes
0x3004
12292
Read the tonemap (high 16 bits)
at the time of transmission
The tonemap is 3 bytes in size and requires two register
descriptions
0x3005
12293
Read the tonemap (lower 16 bits)
when sending
0x3006
12294
Read test results for production
testing
0x3007
12295
Read current band
0: CEN-A 1: CEN-B 3: FCC
0x3008
12296
Read receive SNR for production
test
Not open
0x3009
12297
Reads whether it is currently in
test mode
0: Normal mode 1: Test mode is not open
Reserved ...
...
...
0x3010
12304
Node1's tonemap (high 16 bits)
The tonemap is 3 bytes in size and requires two register
descriptions
0x3011
12305
Node1's tonemap (low 16 bits)
0x3012
12306
Node2's tonemap (high 16 bits)
0x3013
12307
Node2's tonemap (low 16 bits)
0x3014
12308
Node3's tonemap (high 16 bits)
0x3015
12309
Node3's tonemap (low 16 bits)
0x3016
12310
Node4's tonemap (high 16 bits)
0x3017
12311
Node4's tonemap (low 16 bits)
0x3018
12312
Node5's tonemap (high 16 bits)
0x3019
12313
Node5's tonemap (low 16 bits)
0x301A
12314
Node6's tonemap (high 16 bits)
0x301B
12315
Node6's tonemap (low 16 bits)
0x301C
12316
Node7's tonemap (high 16 bits)
0x301D
12317
Node7's tonemap (low 16 bits)
0x301E
12318
Node8's tonemap (high 16 bits)
0x301F
12319
Node8's tonemap (low 16 bits)
0x3020
12320
Node9's tonemap (high 16 bits)
0x3021
12321
Node9's tonemap (low 16 bits)
0x3022
12322
Node10's tonemap (high 16 bits)
0x3023
12323
Node10's tonemap (low 16 bits)