Register description
Register description in bit units (function code 02)
Bit address
Functional description
remark
Hex
Decimal
0x0200
512
Bus arc trip state
The bus arc is faulted and a trip is performed and this bit is set.
Clear the alarm and set it to 0.
0x0201
513
Channel arc trip state
The channel arc is faulted and a trip is performed and this bit is set.
Clear the alarm and set it to 0.
0x0203
515
Bus voltage is too high trip
state
The bus voltage is high and an trip is performed and this bit is set.
Clear the alarm and set it to 0.
0x0204
516
Temperature sensor 1 over
temperature and high trip
state
The temperature sensor 1 overtemperature alarm and performs a
tripping action, this bit is set to 1. Clear alarm after setting 0.
0x0205
517
Temperature sensor 2 over
temperature and high trip
state
The temperature sensor 2 overtemperature alarm and performs a
tripping action, this bit is set to 1. Clear alarm after setting 0.
0x0206
518
Channel reverse current trip
state
This bit is set to 1 when the channel current is reversed and the trip
condition is met and a trip is performed. Clear alarm after setting 0.
0x0207
519
Total reverse current trip
state
The total reverse current alarm and a trip action is performed and
this bit is set. Clear the alarm and set it to 0.
0x0209
521
Total current is too high trip
state
The total current is high and an trip is performed and this bit is set.
Clear the alarm and set it to 0.
0x020A
522
Channel no current trip state
This bit is set to 1 when the channel has no current alarm and the
trip condition is met and a trip is performed. Clear alarm after setting
0
0x020B
523
Channel undercurrent trip
state
This bit is set to 1 when the channel undercurrent alarm is met and
the trip condition is fulfilled and a trip is performed. Clear alarm after
setting 0
0x020C
524
Channel overcurrent trip
state
This bit is set to 1 when the channel is overcurrent and the trip
condition is met and a trip is performed. Clear alarm after setting 0
0x020D
525
Channel current is too low to
trip state
This bit is set to 1 when the channel current is low and the trip
condition is met and a trip is performed. Clear alarm after setting 0
0x020E
526
Channel current is too high
to trip state
This bit is set to 1 when the channel current is high and the trip
condition is met and a trip is performed. Clear alarm after setting 0
0x0210
528
Switch 1 trip status
Switch 1 performs a trip action
0x0211
529
Switch 2 trip status
Switch 2 performs a trip action
0x0212
530
Switch 3 trip status
Switch 3 performs a trip action
0x0213
531
Switch 4 trip status
Switch 4 performs a trip action