USER, INSTALLATION AND SERVICING INSTRUCTIONS

UNIQA.REVOLUTION

  

  

Low temperature wall mounted boiler

EN

TRANSLATION OF THE ORIGINAL INSTRUCTIONS

Содержание UNIQA.REVOLUTION

Страница 1: ...Fonderie SIME S p A 6330326 12 2018 R0 Cod USER INSTALLATION AND SERVICING INSTRUCTIONS UNIQA REVOLUTION Low temperature wall mounted boiler EN TRANSLATION OF THE ORIGINAL INSTRUCTIONS...

Страница 2: ...least one of the fol lowing operations must be carried out set the main system switch to OFF close the gas and water valves for the water heating system In order to ensure optimal appliance operation...

Страница 3: ...supply Do not modify the safety or adjustment devices without authorization and in structions from the manufacturer d IT IS FORBIDDEN Do not block the condensate drain if present Do not pull detach o...

Страница 4: ...tant and useful informa tion MANUAL STRUCTURE This manual is organized as follows CHECKLIST a WARNING Before installing and starting up the boiler make sure you have done the following handle the boil...

Страница 5: ...ng the heating temperature 7 1 5 Adjusting the domestic hot water temperature 7 1 6 Fault malfunction codes 8 2 SHUTDOWN 8 2 1 Temporary shutdown 8 2 2 Shutting down for long periods 9 3 MAINTENANCE 9...

Страница 6: ...tting or value increasing by pressing this button c Programming connector cover plug NOTE pressing any one of these buttons for more than 30 sec onds generates a fault on the display without preventin...

Страница 7: ...e 2 and restore the heating system pressure until the display 1 shows a reading of 1 1 2 bar close the filling valve 2 2 1 Fig 3 select the SUMMER l operating mode by pressing and holding the ybutton...

Страница 8: ...et the main system switch to OFF contact the Qualified Technical Personnel OFF Fig 5 m CAUTION Should you see an alarm not described here contact a qualified technical professional 2 SHUTDOWN 2 1 Temp...

Страница 9: ...d in the INSTALLATION AND MAINTENANCE MANUAL 3 2 External cleaning a WARNING Should it be necessary to access the areas in the bottom part of the appliance make sure that the system components and pip...

Страница 10: ...10...

Страница 11: ...stics 12 5 2 Check and safety devices 12 5 3 Identification 12 5 3 1 Technical Data Plate 13 5 4 Structure 14 5 5 Technical features 15 5 6 Main water circuit 16 5 7 Sensors 17 5 8 Expansion vessel 17...

Страница 12: ...matically every 24 hours if no request for heat has been made domestic hot water comfort function which allows the time necessary for the hot water to become available to be reduced and ensures that t...

Страница 13: ...FACTURE SERIAL NUMBER NAME MAX USEFUL OUTPUT MAX OPERATING PRESSURE MAX HEAT INPUT FLOW RATE MAX OPERATING PRESSURE ELECTRICAL SUPPLY MAXIMUM ABSORBED POWER MAX HEAT INPUT COUNTRY OF INTENDEDINSTALLTI...

Страница 14: ...ater sensor 9 Control panel 10 Domestic hot water heat exchanger 11 Gas valve 12 Domestic water filter and flow regulator 13 System relief valve 14 Boiler drain 15 System pump 16 Water pressure transd...

Страница 15: ...DOMESTIC HOT WATER Domestic hot water energy efficiency class A Domestic hot water energy efficiency 81 Stated domestic hot water profile load XL ELECTRICAL SPECIFICATIONS Power supply voltage V 230...

Страница 16: ...ermal bulb 9 Refrigerant gas high pressure pressure switch 10 Gas valve 11 Domestic hot water flow meter 12 Domestic hot water filter 13 System filling 14 Boiler drain 15 System relief valve 16 System...

Страница 17: ...M UNIQA REVOLU TION Total capacity l 8 0 Prefilling pressure kPa 100 bar 1 0 Useful capacity l 4 0 Maximum system content l 109 Conditions of Average maximum temperature of the system 85 C Start tempe...

Страница 18: ...creasing by pressing this button c Programming connector cover plug NOTE pressing any one of these buttons for more than 30 sec onds generates a fault on the display without preventing boiler operatio...

Страница 19: ...SR Return Probe SIA Air inlet probe APS Air pressure switch EXP Expansion card CP Compressor CR Remote control instead of air thermostat To connect the Air Thermostat or alternatively the Remote Contr...

Страница 20: ...20...

Страница 21: ...meter setting and display 33 7 4 List of parameters 34 7 5 Display of operating data and counters 36 7 6 Gas conversion 37 7 6 1 Preliminary operations 37 7 7 Automatic calibration procedure 38 7 7 1...

Страница 22: ...single unit pro tected by cardboard packaging Fig 15 The plastic bag found inside the packaging contains the follow ing Installation use and maintenance manual Paper template for boiler installation...

Страница 23: ...and accident protection when re moving the packaging and when handling the appli ance Observe the maximum weight that can be lifted per person 6 4 Installation room The room where the appliance is to...

Страница 24: ...is not availa ble replace it with a pump to circulate water in the system and then proceed as described above Once cleaning operations have been carried out and before installing the new appliance it...

Страница 25: ...ied with the accessory itself or are to be found on the packaging 6 10 Gas supply UNIQA REVOLUTION boilers leave the factory specifically prear ranged for G20 gas or G31 The G20 models can be converte...

Страница 26: ...ll smoke outlet The pipes can start from the boiler but the outlets must be concentric or close together no more than 50 cm to be subject to similar wind conditions C32 C32X Concentric roof outlet Out...

Страница 27: ...the presence of the diaphragm modifies the maximum length of the duct as shown below Model Diaphragm Max L m UNIQA REVOLUTION YES 2 5 UNIQA REVOLUTION NO 5 6 11 2 Separate ducts 80mm The smoke outlet...

Страница 28: ...d 10 m inlet 10 m outlet for ducts 80 mm NOTE for the boiler to operate correctly it is necessary that a minimum distance of 0 50 m of the duct is respected with a 90 inlet curve Example calculation o...

Страница 29: ...a 230V 50 Hz network If this cable needs to be replaced an original spare must be re quested from Sime Therefore only the connections of the original components as shown in the table are needed These...

Страница 30: ...ins power is disconnected by setting the main system switch to OFF The manufacturer is not responsible for any damage caused by failure to earth the appliance or failure to ob serve the information pr...

Страница 31: ...R M SE TA CR Fig 34 MULTI ZONE system with zone valve air thermostat and ex ternal sensor TA TZ1 VZ1 VZ2 VZ3 TZ2 TZ3 SE R M Fig 35 m CAUTION Set the parameter tS 17 DELAY SYSTEM PUMP AC TIVATION to al...

Страница 32: ...of the system 4 3 Fig 39 NOTE to completely remove all air from the system it is recom mended that this operation is repeated a number of times check the pressure on the display and if necessary top u...

Страница 33: ...stem is cold is between 1 and 1 2 bar press the button y once for at least 1 second to select SUMMER mode l the value of the delivery sensor detect ed at that moment will appear on the display open on...

Страница 34: ...aximum threshold for deactivating compressor CP 40 PAR 08 External sensor value correction 5 5 C 1 0 PAR 09 DOMESTIC HOT WATER HEATING PAR 10 Boiler antifreeze threshold 0 10 C 1 3 PAR 11 External sen...

Страница 35: ...ery return 10 40 C 1 20 PAR 42 PAR 43 PAR 44 Minimum time between compressor ignitions m 14 PAR 45 Minimum time between compressor on off 13 PAR 46 Return temp threshold for activating the compressor...

Страница 36: ...99 C 1 PAR 06 Actual heating SET temperature Par 13 Par 14 C 1 PAR 07 Power level 0 99 1 PAR 08 Flow meter rate 0 99 l min 0 1 PAR 09 Water pressure transducer reading if resent 0 99 bar 0 1 PAR 10 Re...

Страница 37: ...ventions described set the main system switch to OFF close the gas valve make sure that no hot parts inside the appliance are touched OFF Fig 43 7 6 1 Preliminary operations To carry out the conversio...

Страница 38: ...he gas valve following a fault the electronic board following a fault electrode fan burner and is necessary so that the new components can be identified and can communicate with those already fitted o...

Страница 39: ...5 the modified value will be stored automatically exit the parameter section by pressing and holding down the buttons rand t at the same time approximately 5 seconds until the delivery temperature is...

Страница 40: ...ressure Type of gas G20 G31 Pressure mbar 20 37 Installations with SPLIT and CONCENTRIC flue gas outlet pipe systems Model Heat Output Pressure at nozzles mbar G20 G31 UNIQA REVOLU TION Max 13 3 13 8...

Страница 41: ...press and hold the t button and scroll through the parame ters until you reach PAR 15 press and hold the button to change the value to 0 force minimum power the modified value will be stored automatic...

Страница 42: ...ature is stable To activate the function select parameter PAR 22 see Parameter setting and dis play and set it toa 1 exit parameter settings and press button for approximately 5 seconds until the symb...

Страница 43: ...arts inside the appliance are touched OFF Fig 52 8 2 External cleaning 8 2 1 Cleaning the cladding When cleaning the cladding use a cloth dampened with soap and water or alcohol for stubborn marks d I...

Страница 44: ...pecial care to clean the back part where there is a steel and copper blade 7 7 Fig 56 8 3 4 Checking the ignition detection electrode Check the state of the ignition detection electrode and replace if...

Страница 45: ...te the chimney sweep function described below This function lasts 15 minutes and is activated by proceeding as follows if the panel 2 has not already been removed remove the two screws 1 pull the fron...

Страница 46: ...wer in kW 0 25 0 PAR 02 Hydraulic configuration 5 Low NOx ErP 5 PAR 03 Gas Type Configuration 0 G20 1 LPG 0 or 1 PAR 04 Combustion configuration 3 Low NOx ErP APS 3 To enter Parameter setting and disp...

Страница 47: ...max min absolute limits error Check gas valve and board ALL 78 EV current upper limit error Check gas valve and board ALL 79 EV current lower limit error Check gas valve and board ALL 80 Fault on the...

Страница 48: ...n GJ D H W annual combustible consumption GJ C H seasonal energy efficiency D HW energy efficiency Sound power dB A Specific precautionary measures to be adopted at the time of assembly installation o...

Страница 49: ...d low temperature regime b P1 8 kW At 30 of nominal heat output and low temperature regime 1 97 9 Auxiliary electricity consumption Other items At full load elmax 0 060 kW Standby heat loss Pstby 0 11...

Страница 50: ...50...

Страница 51: ...51...

Страница 52: ...45 Legnago Vr Tel 39 0442 631111 Fax 39 0442 631292 www sime it Fonderie SIME S p A reserves the right to make changes at any time without prior notice in order to improve its products without comprom...