background image

104

4.1

D.H.W. TANK UNIT 

The  enamelled  D.H.W. tank  comes  with  a

magnesium anode to protect the boiler and

an  inspection  flange  for  checking  and  clea-

ning. 

The  magnesium  anode  must  be

checked  annually  and  replaced  if  it  is

worn. 

It  is  advisable  to  place  a  sluice  gate

at  the  entrance  of  the  D.H.W.  tank  unit

which,  apart  from  the  total  closure,  allows

the regulation of the supply capacity.

When  the  boiler  does  not  produce  hot

water,  make  sure  that  the  air  has  been

released  by  acting  on  the  manual  vents

after having turned the main switch off.

4.2

CONTROL OF THE GAS 

PRESSURE UPSTREAM 

OF THE BOILER

If  the  upstream  pressure  is  between  11.5

and 15 mbar the boiler is functioning, thou-

gh  at  an  inferior  maximum  nominal  power.

In  case  of  pressure  less  than  11.5  mbar

the gas pressure switch acts.

4.3

GAS VALVE

The boiler model SIT 845 SIGMA (fig. 14) is

produced with gas valve set at two pressu-

re  values:  maximum  and  minimum,  that

correspond according to the type of gas to

the values indicated in 

Table 2

The  setting  of  the  gas  pressure  at  mini-

mum and maximum values is carried out by

SIME: variations are discouraged. 

Only  in  the  passing  from  one  type  of  gas

supply (methane) to another (propane) is a

change in the working pressure allowed.

Such an operation must be carried out by

authorised  personnel,  or  the  guarantee

will  lose  validity.  Once  the  change  in

working  pressure  has  been  carried  out,

seal the regulators.

When  proceeding  with  the  setting  of  the

pressure,  it  is  necessary  to  follow  a  pre-

es t ablished  or der,  regulating  fir s t  the

MAXIMUM and then the MINIMUM.

4.3.1

Maximum and minimum 

pressure adjustment

In order to carry out the setting of the maxi-

mum proceed in the following way (fig. 15):

–Connect  a  dif ferential  manometer  as

shown in fig. 14.

– Remove  the  plastic  cap  of  the  modula-

tor (1).

–Start  the  boiler  by  pressing  on  the  four

way switch.

–Place the heating potentiometer knob on

the maximum value.

–Using a  ø 10 wrench turn the nut (3) to

find the maximum pressure as shown in

Table 2

: to reduce the pressure turn the

nut  anti-clockwise,  to  increase  the  pres-

sure turn the nut clockwise.

–Turn  of f  and  turn  on  the  burner  2-3

times  to  verify  that  the  pressure  corre-

sponds to the values given in 

Table 2

After  having  regulated  the  maximum  pres-

sure,  proceed  with  the  setting  of  the  mini-

mum pressure.

–Disconnect  the  electric  supply  of  the

modulator.

– With  the  heating  potentiometer  knob  on

the  maximum  value  and  the  burner  alight,

holding the nut (3) blocked, turn the screw

(2)  to  find  the  minimum  pressure  value  as

shown in 

Table 2

: to decrease the pressure

turn the nut anti-clockwise and to increase

the pressure turn the nut clockwise.

–Turn  on  and  turn  of f  the  burner  2-3

times  to  verify  that  the  pressure  corre-

sponds to the values given in 

Table 2

.

–Reconnect  the  electrical  supply  of  the

modulator.

–Replace the plastic cap (1).

4.4

ADJUSTMENT 

OF HEATING 

OUTPUT

To  regulate  the  heat  putput,  modifying  the

fact or y  settings,  which  is  the  minimum

thermal  power  for  each  model (17.8  -  24.1

kW),  it  is  necessary  to  work  with  a  screw-

driver on the trimmer of the heating power

(10 fig. 10). 

To  increase  the  operating  pressure  turn

the  trimmer  in  a  clockwise  direction,  to

decrease the pressure turn the trimmer in

an anti-clockwise direction. 

To facilitate the search for the adjusting of

the  heating  power  the  diagrams  pressu-

re/heat  output  for  natural  gas  (methane)

and  propane  gas  are  available  (figs.  16  -

16/a).  To  ensure  proper  operation,  check

that  the  burner  flame  looks  like  the  one

shown in fig. 17. 

3

2

1

Fig. 15

KEY
1

Plastic cap 

2

Screw regulation minimum pressure

3

Nut regulation maximum pressure

4

USE AND MAINTENANCE

TABLE 2

3

4

2

1

5

Fig. 14

KEY
1

Modulator

2

EV1-EV2 coils

3

Upstream pressure plug

4

Downstream pressure plug 

5

Manometer

22

32 - 32/50 - 32/80

Methane - G20

Maximum burner pressure 

mbar

12,7

12,7

Minimum burner pressure 

mbar

7,3

7,3

Propane - G31

Maximum burner pressure

mbar

28,4

28,4

Minimum burner pressure 

mbar

16,6

16,6

Содержание LOGO 22 OF

Страница 1: ...e boiler is set for operation for the type of gas supplied Check that the flue pipe for the outlet of the products of the combustion is unobstructed Make sure that any shutoff valves are open Make sur...

Страница 2: ...50 D H W tanks LOGO 32 50 OF 32 80 OF central heating and D H W production electronic ignition and modulation natu ral draught Follow the instructions given in this manual for the correct installation...

Страница 3: ...tank unit BT150 version CONNECTIONS M C H flow 3 4 M R C H return 3 4 M E D H W inlet 1 2 M G Gas connection 3 4 M U D H W outlet 1 2 M C Re circulation 1 2 F S1 Safety valve drain 1 2 F S2 D H W tank...

Страница 4: ...D H W circulating pump 10 C H circulating pump 11 Gas valve 12 Burners 13 Non return valve 14 Burners manifold 15 Water pressure transducer 16 Boiler drain cock 17 D H W expansion vessel 18 D H W safe...

Страница 5: ...40 80 40 80 40 80 40 80 D H W setting range C 10 60 10 60 10 60 10 60 Category II2H3P II2H3P II2H3P II2H3P Type B11BS B11BS B11BS B11BS Smokes temperature C 108 110 116 119 Smokes flow gr s 18 5 23 2...

Страница 6: ...W expansion vessel 5 Manual filling group 6 D H W tank 7 D H W tank drain cock 8 Boiler drain cock 9 Burners manifold 10 Pilot burner 11 C H circulating pump 12 Gas valve 13 Gas pressure switch 14 Saf...

Страница 7: ...connect up the boiler you are recommended to make the air cir culating in the piping in order to eliminate any foreign bodies that might be detrimen tal to the operating efficiency of the applian ce...

Страница 8: ...t this operation check that the filling tap is closed 2 5 FLUE The flue for the atmospherical expulsion of the combustion products from natural draught appliances must meet the following requirements...

Страница 9: ...nector ends 3 dama ges irreparably the control panel Before the connection make sure that there is no voltage 2 6 2 Logica Remote Control connection fig 6 pos B The electrical systems must be in com p...

Страница 10: ...on the inspection control and cleaning flange of the tank 2 6 5 Wiring diagram J7 J5 J4 J3 J2 KEY TR Transformer 230 24V TRA Ignition transformer P C H circulating pump PB D H W circulating pump EA I...

Страница 11: ...through a window contact Anti bacterial 2 7 1 Installation The unit must be installed in the main living room For installation follow the assembly instructions inserted in the package At this point w...

Страница 12: ...until it finds the optimum switch off time 59 60 SETTING THE HOT WATER SERVICE PARAMETERS Reduced hot water temperature value Hot water service filling The hot water may be set to a reduced temperatu...

Страница 13: ...witch over to reduced pre set value of the ambient temperature 3 With an external contact it is possible to switch over to reduced pre set value of the antifreeze ambient temperature short circuit 0 0...

Страница 14: ...eginning when the plant is cold and in the subsequent startings This is so to avoid ignitions and switching off with very short intervals that may in particular be found in plants with high losses At...

Страница 15: ...ntinuous jump spark from the electrode is noted despite the pilot burner being lit After 20 seconds the sparking stops the burner goes off and the block signal lights up The cable of the detector elec...

Страница 16: ...PERTURA TA 6 SB 11 SB 12 CIRCUITO CON VALVOLE DI ZONA NOTA I rel vengono impiegati solo nel caso le valvole di zona siano prive di micro L N TA TA1 VZ R VZ1 R1 NOTA PER VERSIONI SOLO RISCALDAMENTO Sos...

Страница 17: ...g potentiometer knob on the maximum value Using a 10 wrench turn the nut 3 to find the maximum pressure as shown in Table 2 to reduce the pressure turn the nut anti clockwise to increase the pres sure...

Страница 18: ...ENANCE Carry out the cleaning of the generator in the following way fig 18 Remove the electricity supply to the boi ler and close the gas supply tap Dismantle the gas group completely Dismantle the li...

Страница 19: ...erature always with the primary circuit controlled between 80 C and 70 C During the entire duration of the testing the hot water taps must remain open After verifying the combustion the boiler should...

Страница 20: ...C and the yellow led of the hot water will light up at the same time In the versions with storage capacity when there is no request for hot water service and heating the leds and are off the operatin...

Страница 21: ...ed Technical Service between April and September The boiler comes with an electricity supply cable which in case of replacement must be requested only from SIME FAULT FINDING Starting failure fig 3 If...

Страница 22: ...hts up To attempt to start the boiler again unscrew the cover of the thermostat and reset the button under neath After 10 minutes from the resetting the boiler will automatically restart For an immedi...

Страница 23: ...he boiler will function by placing the selector on the o position obviously without consequent control of the room temperature The functioning instructions are inside the lid fig 9 Every setting or mo...

Страница 24: ...l lowing list of items one after the other are displayed The thermo feeler continues to function independently of the display Day hour room temperature External temperature Hot water service temperatu...

Страница 25: ...ity boiler unit temperature desired for hot water service at reduced level To have access to the reduced hot water service temperature parameter press the and keys at the same time for at least 5 seco...

Страница 26: ...rature set in parameter 3 1 standard Hot water according to the daily heating programme In the comfort periods of the heating the temperature of the boiler unit is regulated at the value set via para...

Страница 27: ...ode Current values Display and setting of the gradient of the heating characteristics curve When the room temperature set is not reached choose the gradient indicated in point 2 7 3 Display of the cur...

Страница 28: ...oning by acting on the filling tap of the boiler fig 4 Plant overpressure Call the Authorised Technical Service for assistance Thermostat safety interception Call the Authorised Technical Service for...

Отзывы: