2.7

LOGICA REMOTE CONTROL

All the boiler's functions can be managed by

a optional digital multifunctional device code

8092204 for the remote of the boiler itself

and for regulating room climatic conditions

with an operational reserve of 12 hours.

The heating circuit is controlled by the room

temperature  sensor  built-in  the  equipment

or  by  the  atmospheric  conditions,  with  or

without environmental inflow, if the boiler is

connected to an external sensor.

Characteristics:

–Ergonomic control unit divided according

to function (control levels)).

–Clear division of basic functions:

operating  regime,  correction  of  set

value and presence button are directly

accessible;

Dif fer ent  r eal  curr ent  values  ar e

accessible through the "info" button;

other  functions  can  be  programmed

after the cover has been opened;

special  service  level  with  protected

access;

–Each  setting  or  modification  is  displayed

and confirmed.

–Tome  setting  (special  line  for  changing

BST/CET).

–Heating programme with max. 3 heating

periods per day, individually selectable.

– Copy  function  for  easy  transfer  of  hea-

ting  programme  to  the  next  or  pre-

vious day.

–Holiday  programme:  the  programme  is

interrupted  for  the  holiday  period  and

automatically  restar ted  on  returning

home.

–Option to return the heating program to

default values.

–Programming lock (child safety).

Functions:

–Delivery  temperature  control  guided  by

the  atmospheric  conditions,  taking  into

account the dynamics of the building.

–Delivery  temperature  control  guided  by

atmospheric  conditions  with  influence  of

ambient temperature.

–Ambient temperature control only.

–Adjustable influence of ambient tempera-

ture shift .

–Switch-on and switch-off optimisation.

–Rapid lowering.

–ECO functions (daily heating limiter, auto-

matic summer/winter switch-over).

–Controllable  maximum  delivery  tempera-

ture limit (specifically for floor plants).

–Limitation  of  increase  in  pre-set  delivery

temperature.

–Anti-freeze protection for buildings.

–Hourly  programming  of  the  tank  unit

temperature  on  two  levels:  comfort  and

reduced.

–Domestic hot water control with nominal

value requirement and enable.

–Connection to room sensor or switching

of operating regime through the telepho-

ne  sys t em  wit h  ext ernal  cont act  or

through a window contact.

–Anti-bacterial.

2.7.1

Installation

The unit must be installed in the main living

room.  For  installation,  follow  the  assembly

instructions inserted in the package. 

At  this  point,  with  the  selector  knob  on

(

),  the  installer  can  adjust  the  basic

parameters settings according to the indi-

vidual needs. 

If  there  is  a  thermostatic  radiator  valve

fitted, this must be set to maximum.

2.7.2

Installation settings

The  settings  for  the  basic  operating  para-

meters for individual needs are reported in

the  instruction  leaflet  supplied  with  the

"Logica Remote Control" and in the section

reserved for the user in this manual.

For  further  adjustments  which  can  be  car-

ried out by the installer, the "Logica Remote

Control"  offers  a  level  of  service  and  para-

meterising  which  can  only  be  accessed

through a special combination of buttons.

To  activate  this  level  of  service  or  parame-

terising  press  buttons

and 

least

5 seconds. This will activate the paramete-

rising  level.  Then  use  the  same  arrow  but-

tons  to  select  the  individual  input  lines  and

adjust the values with

or 

.

98

Antifreeze protection 

"Pre-set ambient 

temperature value"

Summer/Winter switch-over 

temperature

Type of control:

0 = with ambient influence

1 = without ambient influence

Influence of ambient temperature

Heating takes place up to this pre-set value if the plant is activated in standby

(e.g. holidays). 

In this way, the building antifreeze function is active, preventing an excessive

lowering of the ambient.

This parameter regulates the temperature of the automatic summer/win-

ter switch-over.

This  parameter  de-activates  the  ambient  influence  and  as  a  result  all  the

optimisations and adaptations. 

If a valid external temperature is not transmitted , the controller switches to

the  pure ambient control guide variable.

If the ambient controller is used only as a remote control (placed in the refe-

rence room and without an external sensor connected), the value must be

set at 0 (zero). 

If  the  change  in  ambient  temperature  from  the  pre-set  value  remains  high

during the entire day, the influence must be increased. If the ambient tem-

perature is around the pre-set value (control oscillation), the influence must

be reduced. 

Note: If the ambient temperature influence constant is set at 0, the adap-

tation of the heating curve is deactivated. In this case, parameter 57 will

have no effect at all.

54

HEATING CIRCUIT SETTINGS

52

53

51

Содержание LOGO 22 OF

Страница 1: ...e boiler is set for operation for the type of gas supplied Check that the flue pipe for the outlet of the products of the combustion is unobstructed Make sure that any shutoff valves are open Make sur...

Страница 2: ...50 D H W tanks LOGO 32 50 OF 32 80 OF central heating and D H W production electronic ignition and modulation natu ral draught Follow the instructions given in this manual for the correct installation...

Страница 3: ...tank unit BT150 version CONNECTIONS M C H flow 3 4 M R C H return 3 4 M E D H W inlet 1 2 M G Gas connection 3 4 M U D H W outlet 1 2 M C Re circulation 1 2 F S1 Safety valve drain 1 2 F S2 D H W tank...

Страница 4: ...D H W circulating pump 10 C H circulating pump 11 Gas valve 12 Burners 13 Non return valve 14 Burners manifold 15 Water pressure transducer 16 Boiler drain cock 17 D H W expansion vessel 18 D H W safe...

Страница 5: ...40 80 40 80 40 80 40 80 D H W setting range C 10 60 10 60 10 60 10 60 Category II2H3P II2H3P II2H3P II2H3P Type B11BS B11BS B11BS B11BS Smokes temperature C 108 110 116 119 Smokes flow gr s 18 5 23 2...

Страница 6: ...W expansion vessel 5 Manual filling group 6 D H W tank 7 D H W tank drain cock 8 Boiler drain cock 9 Burners manifold 10 Pilot burner 11 C H circulating pump 12 Gas valve 13 Gas pressure switch 14 Saf...

Страница 7: ...connect up the boiler you are recommended to make the air cir culating in the piping in order to eliminate any foreign bodies that might be detrimen tal to the operating efficiency of the applian ce...

Страница 8: ...t this operation check that the filling tap is closed 2 5 FLUE The flue for the atmospherical expulsion of the combustion products from natural draught appliances must meet the following requirements...

Страница 9: ...nector ends 3 dama ges irreparably the control panel Before the connection make sure that there is no voltage 2 6 2 Logica Remote Control connection fig 6 pos B The electrical systems must be in com p...

Страница 10: ...on the inspection control and cleaning flange of the tank 2 6 5 Wiring diagram J7 J5 J4 J3 J2 KEY TR Transformer 230 24V TRA Ignition transformer P C H circulating pump PB D H W circulating pump EA I...

Страница 11: ...through a window contact Anti bacterial 2 7 1 Installation The unit must be installed in the main living room For installation follow the assembly instructions inserted in the package At this point w...

Страница 12: ...until it finds the optimum switch off time 59 60 SETTING THE HOT WATER SERVICE PARAMETERS Reduced hot water temperature value Hot water service filling The hot water may be set to a reduced temperatu...

Страница 13: ...witch over to reduced pre set value of the ambient temperature 3 With an external contact it is possible to switch over to reduced pre set value of the antifreeze ambient temperature short circuit 0 0...

Страница 14: ...eginning when the plant is cold and in the subsequent startings This is so to avoid ignitions and switching off with very short intervals that may in particular be found in plants with high losses At...

Страница 15: ...ntinuous jump spark from the electrode is noted despite the pilot burner being lit After 20 seconds the sparking stops the burner goes off and the block signal lights up The cable of the detector elec...

Страница 16: ...PERTURA TA 6 SB 11 SB 12 CIRCUITO CON VALVOLE DI ZONA NOTA I rel vengono impiegati solo nel caso le valvole di zona siano prive di micro L N TA TA1 VZ R VZ1 R1 NOTA PER VERSIONI SOLO RISCALDAMENTO Sos...

Страница 17: ...g potentiometer knob on the maximum value Using a 10 wrench turn the nut 3 to find the maximum pressure as shown in Table 2 to reduce the pressure turn the nut anti clockwise to increase the pres sure...

Страница 18: ...ENANCE Carry out the cleaning of the generator in the following way fig 18 Remove the electricity supply to the boi ler and close the gas supply tap Dismantle the gas group completely Dismantle the li...

Страница 19: ...erature always with the primary circuit controlled between 80 C and 70 C During the entire duration of the testing the hot water taps must remain open After verifying the combustion the boiler should...

Страница 20: ...C and the yellow led of the hot water will light up at the same time In the versions with storage capacity when there is no request for hot water service and heating the leds and are off the operatin...

Страница 21: ...ed Technical Service between April and September The boiler comes with an electricity supply cable which in case of replacement must be requested only from SIME FAULT FINDING Starting failure fig 3 If...

Страница 22: ...hts up To attempt to start the boiler again unscrew the cover of the thermostat and reset the button under neath After 10 minutes from the resetting the boiler will automatically restart For an immedi...

Страница 23: ...he boiler will function by placing the selector on the o position obviously without consequent control of the room temperature The functioning instructions are inside the lid fig 9 Every setting or mo...

Страница 24: ...l lowing list of items one after the other are displayed The thermo feeler continues to function independently of the display Day hour room temperature External temperature Hot water service temperatu...

Страница 25: ...ity boiler unit temperature desired for hot water service at reduced level To have access to the reduced hot water service temperature parameter press the and keys at the same time for at least 5 seco...

Страница 26: ...rature set in parameter 3 1 standard Hot water according to the daily heating programme In the comfort periods of the heating the temperature of the boiler unit is regulated at the value set via para...

Страница 27: ...ode Current values Display and setting of the gradient of the heating characteristics curve When the room temperature set is not reached choose the gradient indicated in point 2 7 3 Display of the cur...

Страница 28: ...oning by acting on the filling tap of the boiler fig 4 Plant overpressure Call the Authorised Technical Service for assistance Thermostat safety interception Call the Authorised Technical Service for...

Отзывы: