background image

Service

Condenser unit operation

The condensing unit is weatherproof and equipped to operate in ambient temperatures from  – 20°F – 130°F 
(– 29°C – 54.4°C). A dual pressure control provides compressor protection from excessive head pressures, 
pumps the refrigeration system down and shuts the condensing unit off when the solenoid valve on the 
evaporator unit is closed.

Low ambient operation: Reliable operation at low ambient temperature is achieved with a pumpdown cycle, a 
crankcase heater and a head pressure control valve. As the ambient temperature falls and the head pressure 
decreases the valve maintains a minimum head pressure of 215 psi by bypassing discharge gas around the 
condenser to the receiver to increase the pressure at the condenser outlet. This backs liquid refrigerant up in the 
condenser to reduce the area available for condensing which increases the head pressure to maintain the 215 
psi set point. A check valve is installed in the liquid line between the receiver and the condenser to prevent liquid 
migration from the receiver to the condenser during the off cycle. The crankcase heater works in conjunction with 
a continuous pumpdown cycle to prevent accumulation of liquid refrigerant in the compressor oil during the off 
c

This prevents compressor damage due to a flooded compressor start. The low pressure control will start the 

condensing unit anytime the low side pressure rises above the 30 psi set point and pump the refrigerant out until 
the pressure falls to 10 psi. The crankcase heater, which is energized whenever the condensing unit has power, 
keeps the compressor oil warmer than the coldest location in the system. This minimizes off cycle refrigerant 
migration. If power to the condensing unit is interrupted after the system is charged the compressor should not be 
started unless the crankcase heater has been energized for at least four hours immediately prior to compressor 
startup. However the compressor can safely be started during the refrigeration system charging process (without 
the warm-up period) once sufficient refrigerant is in the system to maintain a positive pressure on the suction side 
of the compressor.  

   

Evaporator unit operation

Follett’s icemaker consists of four distinct functional systems:

 1. 

Refrigeration 

system

2.  Electrical control system
3. Water 

system

4. Harvesting 

system 

These four systems work together to accomplish the production and harvesting of ice. A problem in any one 
of these systems will result in improper operation of the entire ice production cycle. When troubleshooting the 
icemaker, it is important to analyze the entire system operation to determine which system is not functioning 
properly, then pinpoint the component within that system that is malfunctioning. Determine what corrective action 
must be taken before making any adjustments or replacing any components.

The icemaking process

The Follett icemaker uses a stainless steel jacketed evaporator and operates on a continuous freezing cycle. Water is 
supplied to the evaporator from the water reservoir where the water level is controlled by a float valve. This valve also 
shuts off the water supply when the icemaker is not running. 

When the icemaker is running, a layer of ice forms on the interior surface of the evaporator. This ice is continuously 
removed by a slowly rotating (12 RPM) auger. The auger carries the ice upward into the cavity formed by the top 
bearing housing and the compression loop, where it is compressed to remove excess water. When the ice reaches 
the desired hardness it rotates within the cavity and is forced through a discharge port and compression nozzle and 
into the ice transport tube. The discharge tube and compression nozzle are slightly restricted to further compress the 
ice and produce the desired hardness. As the formation of ice continues, ice in the transport tube is pushed through 
the tube to the storage compartment in the ice dispenser or ice storage bin.

A solid state control board located in the electrical box of the icemaker controls the normal operation of the icemaker 
and monitors gearmotor torque. This control board will shut down the icemaker should an over-torque condition 
occur. It is very important that you familiarize yourself with the operational sequences detailed in this manual before 
attempting to service the icemaker.

12

Содержание MC825 Series

Страница 1: ...eries Icemaker with Remote Condensing Unit 00108647R03 801 Church Lane Easton PA 18040 USA Toll free 800 523 9361 610 252 7301 Fax 610 250 0696 www follettice com Order parts online www follettice com...

Страница 2: ...eturn Policy Follett equipment may be returned for credit under the following conditions 1 The equipment is new and unused 2 A return authorization number has been issued by customer service within 30...

Страница 3: ...ire technical help at any point please call our technical service group 800 523 9361 or 610 252 7301 Before you begin After uncrating and removing all packing material inspect the equipment for concea...

Страница 4: ...e Power cord Water line 3 8 OD tubing Drain 3 4 MPT Evaporator connections High pressure line liquid line Power connection Low pressure line suction line NEMA 5 15 Service loop 24 25 616mm Condenser u...

Страница 5: ...ote The service loop is not included when calculating the length rise or drop of the tubing run Water pressure 10 psi 70 psi Water temperature 50 F 90 F 10 C 32 C Install condenser unit Mount condense...

Страница 6: ...for service 2 Position icemaker on bin a If new storage bin and icemaker position icemaker with connections facing rear of bin b If using existing bin place supplied gasket 2 5 64mm from front of bin...

Страница 7: ...sing problems Follow guidelines below to ensure correct installation Call factory for assistance if you are unable to meet these requirements Note If connecting an MC825 evaporator unit to a manually...

Страница 8: ...of the refrigeration line set must be USA Government Environmental Protection Agency EPA certified in proper refrigerant handling and servicing procedures A qualified person must perform all roof or w...

Страница 9: ...system for up to 50 ft 15 2m line length See chart below for line length longer than 50 ft 15 2m 10 Insulate entire suction line including shut off valves to prevent condensation 11 Adjust the condens...

Страница 10: ...eaner or equivalent Solution temperature must be at least 120 F 48 9 C 1 Remove evaporator unit panels required to gain access to water reservoir components Fig 7 and electrical control box Fig 8 2 Tu...

Страница 11: ...itizing solution from reservoir through float evaporator drain line Fig 7 1 19 Fill reservoir Fig 7 2 with 120 F 49 C water Empty water through float evaporator drain line Fig 7 1 Repeat 3 times 20 Tu...

Страница 12: ...rigerant is in the system to maintain a positive pressure on the suction side of the compressor Evaporator unit operation Follett s icemaker consists of four distinct functional systems 1 Refrigeratio...

Страница 13: ...service port Check valve Receiver 14 pounds Filter drier with sight glass Low side refrigeration line run Low side service valve with service port High side refrigeration line run High side service va...

Страница 14: ...ITE 115 VAC 60 HZ BLACK WHITE GREEN x WHITE BLACK FAN DRV L1 L2 9 B 7 A WHITE BLUE PURPLE WHITE L2 COMP L1 3 6 1 4 WHITE BLACK BLACK WHITE DR CORD SIGNAL BLACK BIN WHITE 60M HIGH VOLTAGE BIN COMP HP S...

Страница 15: ...Water level Water level Evaporator drains Shut off valve Strainer Evaporator service drain Water in Water system diagram Water inlet Auger Compression nozzle Ice tranport tube Evaporator port Harvest...

Страница 16: ...t be used In the event of system contamination for example a compressor burn out refrigerant leak presence of non condensibles or moisture the system must be repaired evacuated and recharged using vir...

Страница 17: ...r checks for water in the reservoir The Bin Empty LED B E will be on The high voltage bin signal connection is used on all Follett ice dispenser applications The high voltage terminals respond to appl...

Страница 18: ...SIGNAL BLACK BIN WHITE RED RED WATER COMPRESSOR SENSOR SWITCH RESET BIN LOW V COMP FAN DRV HP SW COMP HIGH VOLTAGE BIN L1 L2 WTR PROBE WTR PROBE BIN LOW V FAN DRV L2 COMP L1 60M HIGH VOLTAGE BIN COMP...

Страница 19: ...OLTAGE BIN L1 L2 WTR PROBE WTR PROBE BIN LOW V FAN DRV L2 COMP L1 60M HIGH VOLTAGE BIN COMP HP SW B T WTR 2ND B E PWR RESET DR 20M C 60M B T WTR 2ND B E PWR DR 20M C 19 Normal operation Stage 3 Refrig...

Страница 20: ...LOW V FAN DRV L2 COMP L1 60M HIGH VOLTAGE BIN COMP HP SW B T WTR 2ND B E PWR RESET DR 20M C 60M B T WTR 2ND B E PWR DR 20M C 20 Normal operation Stage 4 Ice bin full The ice level control opens the B...

Страница 21: ...LACK WHITE CORD SIGNAL BLACK BIN WHITE RED RED WATER COMPRESSOR SENSOR SWITCH RESET BIN LOW V COMP FAN DRV HP SW COMP HIGH VOLTAGE BIN L1 L2 WTR PROBE WTR PROBE BIN LOW V FAN DRV L2 COMP L1 60M HIGH V...

Страница 22: ...L BLACK BIN WHITE RED RED WATER COMPRESSOR SENSOR SWITCH RESET BIN LOW V COMP FAN DRV HP SW COMP HIGH VOLTAGE BIN L1 L2 WTR PROBE WTR PROBE BIN LOW V FAN DRV L2 COMP L1 60M HIGH VOLTAGE BIN COMP HP SW...

Страница 23: ...the reset button Diagnostic sequence no water If the water level in the float reservoir drops too low three things happen 1 The WTR light is turned OFF 2 The ice machine shuts down 3 The BT light turn...

Страница 24: ...well 2 Install drain pan and evaporator mounting base 3 Fill gearmotor shaft well with food grade grease 4 Install condensate shield and seat against gearmotor boss 5 Install bearing O ring in groove...

Страница 25: ...llow 20 minutes to make sure icemaker restarts Verify integrity of water supply 1 Replace control board 2 Test replace gearmotor Refer to torque out troubleshooting Troubleshooting Problem No ice prod...

Страница 26: ...essor 10 Faulty expansion valve s 1 Clean evaporator with liquid icemaker cleaner 2 Clean condenser 3 Remove obstruction 4 Verify ice production capacity 5 Replace condenser fan 6 Check for leaks repa...

Страница 27: ...r runs briefly draws approximately 10 to 11 amps 1 Mineral build up on evaporator surface 2 Kink in ice transport tube 3 Ice transport tube ruptured internally 4 Worn evaporator bearings 5 Bin level c...

Страница 28: ...10452 2 Panel rear 00110460 3 Panel right side 00110478 4 Panel left side 00110486 5 Panel front remote 00110494 6 Panel front top mount 00110502 7 Base evaporator unit 00110510 8 Grommet ice 501921 9...

Страница 29: ...ion TXV bulb 00106534 11 Sight glass 00107045 12 Coil solenoid valve 00112847 13 Ice compression nozzle 502220 14 Reservoir water line 502079 15 Service valve 00107060 Not shown Evaporator water feed...

Страница 30: ...shown Transport tube sold by the foot 500366 Not shown Transport tube insulation sold by the foot 501176 Not shown Follett QC4 FL4S water filter system includes FL4S primary cartridge AFSYSTMFL43 and...

Страница 31: ...3 502733 12 Bolt mounting base 502227 13 Gearbox motor assembly 502730 14 Compression nozzle with double drain 502220 16 Drain pan evaporator 502727 17 Clamp compression nozzle and screw 502226 18 Tub...

Страница 32: ...iver 00110627 7 Receiver service valve 00110692 8 Service valve suction line 00110643 9 Condenser 00110668 10 Condenser fan motor 00110601 Not shown Condenser fan blade 00123067 11 Condenser fan guard...

Отзывы: