76
Device data
1.
>
device data
>
F-station
>
drain. time
2. In menu
drain. time
enter the desired time.
5.5.1.2
Entering turn-on and turn-off delay
The values for turn-on or turn-off delay may only be changed
after consultation with service personnel. 0.1 s-steps can be
keyed in.
1.
>
device data
>
F-station
>
t. on
resp.
t. off delay
2. In menu
t. on delay
enter the desired time.
3. In menu
t. off delay
proceed as with
t. on delay
.
The pumps are switched on only after the turn-on delay has
lapsed.
For those animals breaking off feed intake for a short time, the
turn-off delay prevents the valves from switching on and off con-
tinuously or the peristaltic pumps from running up or shutting
down.
5.5.1.3
Pump start and stop
The value for
pump start
determines the time within which a
non-operative peristaltic pump runs up to its maximum speed.
The value for
pump stop
determines the period of time needed
by a peristaltic pump to shut down from its maximum speed to a
non-operative state. Usually the values in the menus
pump start
and
stop
remain unchanged.
1.
>
device data
>
F-station
>
pump start
resp.
pump
stop
2. In
pump start
enter the desired period of time.
3. In
pump stop
enter the desired value.
<station 1>
drain. time: [16]sec
...
<station 1>
...
t. on delay: [0.2]sec
t. off delay: 0.2 sec
...
<station 1>
...
pump start: [0.2]sec
pump stop: 0.2 sec
...
Содержание TAK5-CH1-25
Страница 38: ...38 Operation ...
Страница 54: ...54 Start up ...
Страница 70: ...70 Setup ...
Страница 84: ...84 Device data ...
Страница 90: ...90 Calibration ...
Страница 150: ...150 Cleaning ...
Страница 170: ...170 Animal control ...
Страница 192: ...192 Failures and warnings ...
Страница 196: ...196 Care and maintenance plan Routine tasks ...
Страница 215: ......
Страница 218: ...218 Annex 16 3 5 Template for individual feeding plan ...
Страница 219: ...Annex 219 16 4 Basic principle of interval feeding ...
Страница 222: ...222 Annex ...