Versiv Cabling Certification Product Family
Users Manual
114
GPU140.EPS
Figure 44. Screen to Set the Number of Connectors,
Splices, and Jumpers
Total Connections
: Enter the total number of connections that
are in each path of the link. Do not adjust the number for the
Reference Method
you use. For example, if the link has 3
connections, enter “3” even if you use the
2
or
3 Jumper
reference method. When the tester calculates the loss limit, it
automatically removes the losses of the connections you used
to set the reference.
Note
For links with MPO modules, each module is one
connector.
D
A
C
H
G
E
B
F