![Fluke E1M Скачать руководство пользователя страница 73](http://html1.mh-extra.com/html/fluke/e1m/e1m_user-manual_2309862073.webp)
EthernNet/IP
Output Data
73
10
10.4 Output Data
Once the pyrometer has been initialized and is running in the data exchange mode, only the below listed
parameters can be changed, using the device’s output data.
Table 10-3: Output Data
Address without offset
Length
Format
Value
0
1 Byte
BYTE
Type of parameter
1
4 Byte
REAL / UDINT
Parameter
The <Type of parameter> gives the meaning of the following parameters with the same format as described in
section 10.2
Table 10-4: Parameter Types
Type of parameter
Meaning
Format
0
Does not change anything
-
1
Slope
REAL
2
Emissivity
REAL
3
Transmissivity
REAL
4
Averaging time
REAL
5
Peak hold time
REAL
6
Valley hold time
REAL
7
Set point for the relay
REAL
8
Laser/LED control
UDINT
To send the parameters and their values to the device, they must be stored in the controller tags first and then
copied to their destination register in the device. Please note, that most of the values of the parameters are REALs
whereas the parameter for laser control uses UDINT format
– at least this value must be stored in a separate tag.
10.5 Diagnostics
The EtherNet/IP device has a designated status register. The bits of this register make up for an error code, which
is sent as a part of input data.
0x05
Status
DWORD
4 Byte
It can be translated using the table below.
Содержание E1M
Страница 113: ...Accessories Mechanical Accessories 113 12...