Patch Cord Test Results 

 

 

 

 

bal25.bmp 

Low-frequency return loss failure 

caused by bad cable 

 

bal26.bmp 

High frequency return loss failure  

caused by a bad plug 

Figure 2. Return Loss Failures at Low and High Frequencies 

NEXT Failures 

NEXT failures are typically caused by the following: 

 

Excessive untwisting of pairs at plug. Most NEXT failures occur at plugs, where the 
twist in the wire pairs is interrupted. 

 

Poor quality plug 

 

Poor quality cable  

 

Poorly matched plug and jack (Cat 6/Class E applications) 

 

Cable compression (pinches, kinks, etc.) 

 

Excessive noise source near cabling under test. Use the impulse noise test to check 
for noise. 

 

Wrong test limit selected 

Fault Information for Long Patch Cords 

For 20 m patch cord limits, the tester's automatic diagnostics may help you determine 
why a patch cord failed. After an Autotest that failed, press 

J

 Fault Info to see 

information about the failure.  

Note 

The tester's automatic diagnostics do not usually give complete fault 
information for patch cords shorter than 20 m.  

Содержание DTX-PCU6S

Страница 1: ...DTX PCU6S Patch Cord Adapters Users Manual November 2004 2004 Fluke Corporation All rights reserved All product names are trademarks of their respective companies...

Страница 2: ...eturned to a Fluke Networks authorized service center within the warranty period To obtain warranty service contact your nearest Fluke Networks authorized service center to obtain return authorization...

Страница 3: ...hy Patch Cords Fail 5 Wire Map Failures 6 Return Loss Failures 6 NEXT Failures 7 Fault Information for Long Patch Cords 7 Mechanical Stress Tests for Patch Cords 8 Replacing the Adapter s Jacks 8 When...

Страница 4: ...ii DTX PCU6S Patch Cord Adapters Users Manual...

Страница 5: ...1 Replacement Parts 9 C 1 Cat 5e Patch Cord Limits per TIA EIA 568 B C 1 C 2 Cat 6 Patch Cord Limits per TIA EIA 568 B C 2 C 3 Cat 5e Patch Cord Limits per ISO IEC 11801 2002 C 2 C 4 Cat 6 Patch Cord...

Страница 6: ...iv DTX PCU6S Patch Cord Adapters Users Manual...

Страница 7: ...le Page 1 Patch Cord Test Connections 5 2 Return Los Failures and Low and High Frequencies 7 3 Replacing the RJ45 Jack 9 4 Measurement Accuracy of the DTX PCU6S Patch Cord Test Configuration 10 B 1 Pr...

Страница 8: ...vi DTX PCU6S Patch Cord Adapters Users Manual...

Страница 9: ...priate standards organization for details Contact Fluke Networks for general information on standards and for DTX software or database updates that may result from changes to standards The patch cord...

Страница 10: ...2 539 6311 Singapore 65 6738 5655 Taiwan 886 2 227 83199 USA 1 800 283 5853 Anywhere in the world 1 425 446 4519 Visit our website for a complete list of phone numbers Additional Resources for Cable...

Страница 11: ...ware to install new software into the DTX testers See the DTX CableAnalyzer Users Manual the DTX CableAnalyzer Technical Reference Handbook or the online help in LinkWare for instructions Note Patch c...

Страница 12: ...ttach the DTX PCU6 SR adapter to the remote DTX tester 2 Turn the rotary switch to SETUP then select Twisted Pair 3 On the Twisted Pair menu select Cable Type 4 Select the category of twisted pair cab...

Страница 13: ...Note NEXT loss and return loss are measured in one direction only as required by the patch cord test standard For standard patch cords up to 5 m this method is adequate and can detect performance pro...

Страница 14: ...nges in impedance Excessive untwisting of pairs at plug Poor quality plug Cable impedance not uniform poor quality cable Cable compression pinches kinks etc Poorly matched plug and jack most often aff...

Страница 15: ...oor quality plug Poor quality cable Poorly matched plug and jack Cat 6 Class E applications Cable compression pinches kinks etc Excessive noise source near cabling under test Use the impulse noise tes...

Страница 16: ...s may be worn away however continuous use wipes off the oxidation and extends the life of the contacts WCaution Testing patch cords that have poorly crimped plugs may reduce the life of the patch cord...

Страница 17: ...rs performance See Appendix A Insulation displacement connectors in RJ45 jack Connectors on circuit board h bal11f eps Figure 3 Replacing the RJ45 Jack Replacement Parts Table 1 shows the replacement...

Страница 18: ...ation The results were computed using the methods defined in standards applicable to field tester requirements The accuracies shown reflect the accuracy of the measurement circuitry excluding variabil...

Страница 19: ...erize the adapters and determine if they are working properly DTX PCU6S Performance Test Using a Reference Patch Cord When you first receive your adapters you should test a patch cord and save the cor...

Страница 20: ...patch cord go to the correct testers 2 Run an Autotest then save the results 3 Compare the results with the reference patch cord s previous results The difference between the old and new NEXT and RL r...

Страница 21: ...patch cord test limit with the shortest length If you are testing Cat 5e plugs and have replaced the adapters jacks with Cat 5e jacks select the Cat 5e limit with the shortest length Run the NEXT and...

Страница 22: ...DTX PCU6S Patch Cord Adapters Users Manual B 2...

Страница 23: ...e Replacing the Adapter s Jacks on page 8 for installation instructions Table C 1 Cat 5e Patch Cord Limits per TIA EIA 568 B Patch Cord Length and NEXT dB Freq MHz 0 5m 1m 1 5m 2m 2 5m 3m 3 5m 4m 5m 7...

Страница 24: ...38 08 37 79 37 64 37 55 37 55 14 0 Note Patch cord performance requirements for CENELEC standards CLC limits are equivalent to those for ISO IEC standards except that CENELEC standards have no requir...

Страница 25: ...57 63 57 06 23 4 20 61 60 53 60 11 59 75 59 42 59 12 58 85 58 6 58 17 57 32 56 71 55 88 55 36 23 7 25 59 08 58 62 58 21 57 85 57 53 57 24 56 98 56 74 56 32 55 5 54 92 54 15 53 68 24 0 31 25 57 16 56...

Отзывы: