DTX-MFM2/GFM2/SFM2 Fiber Modules
Users Manual
32
Autotest in Far End Source Mode
Use Far End Source mode to measure loss at one
wavelength on individual fibers.
Far End Source mode requires a stand-alone optical
source. Figure 13 shows the equipment required for
testing fiber in Far End Source mode.
amd51f.eps
A
Tester and smart remote with fiber modules and
connector adapters installed (match connector adapters
to the connectors in the link)
B
Memory card (optional)
C
Two AC adapters with line cords (optional)
D
Reference test cord. Match the fiber to be tested. SC
connector at one end. Match the link connectors at the
other end.
E
Reference test cord. Match the fiber and connectors in
the link.
F
Mandrel. Recommended when testing multimode fiber
with a DTX-MFM2 module. See page 12.
G
Fiber cleaning supplies
Figure 13. Equipment for Testing in Far End Source Mode (Method B)
Содержание DTX-GFM2
Страница 15: ...Installing the Connector Adapter 9 amd99f eps Figure 4 Installing the Connector Adapter...
Страница 29: ...Certifying Fiber Cabling 23 amd145f eps Figure 8 Smart Remote Mode Reference Connections Method B...
Страница 31: ...Certifying Fiber Cabling 25 amd146f eps Figure 9 Smart Remote Mode Test Connections Method B...
Страница 35: ...Certifying Fiber Cabling 29 amd147f eps Figure 11 Loopback Mode Reference Connections Method B...
Страница 37: ...Certifying Fiber Cabling 31 amd148f eps Figure 12 Loopback Mode Test Connections Method B...
Страница 41: ...Certifying Fiber Cabling 35 amd149f eps Figure 14 Far End Source Mode Reference Connections Method B...
Страница 45: ...Using the Visual Fault Locator 39 amd23f eps Figure 17 Using the Visual Fault Locator...
Страница 48: ...DTX MFM2 GFM2 SFM2 Fiber Modules Users Manual 42 amd58f eps Figure 19 Connections for Monitoring Optical Power...
Страница 60: ...DTX MFM2 GFM2 SFM2 Fiber Modules Users Manual B 4...