Versiv Series Cabling Certification Product Family
Technical Reference Handbook
204
How to Use the Measurement Cursor on the
HDTDR and HDTDX Plot
You can use the cursor on the HDTDR and HDTDX plots to
measure the distance to a source of high return loss or crosstalk
from any point on the plot. You can also measure the length of a
segment or patch cord that causes high return loss or crosstalk.
To use the measurement cursor to measure distance
Refer to Figure 90.
1
Tap the yellow circle at the top of the cursor (
) so that
MARK
shows.
2
While
MARK
shows, use one of these methods to move the
cursor to the point where you want to start the measurement:
Drag the cursor with the yellow circle (
).
Tap or press and hold
or
(
).
3
Tap
MARK
, then while
UNMARK
shows, move the cursor to
the point where you want to end the measurement.
Note
If UNMARK and the cursor controls do not show, tap
the yellow circle.
The distance between the cursor and the mark shows below the
plot (
).
4
To make a new measurement, tap the yellow circle, tap
UNMARK
(
), then do steps 1, 2, and 3 again.
Содержание CableAnalyzer DSX-5000
Страница 24: ...xxii Versiv Series Cabling Certification Product Family Technical Reference Handbook...
Страница 34: ...xxxii Versiv Series Cabling Certification Product Family Technical Reference Handbook...
Страница 153: ...Chapter 3 Certify Twisted Pair Cabling Frequency Domain Results 117 GPU70 PNG Figure 47 Twisted Pair Insertion Loss Plot...
Страница 157: ...Chapter 3 Certify Twisted Pair Cabling Frequency Domain Results 121 GPU158 PNG Figure 50 Twisted Pair Impedance Results...
Страница 159: ...Chapter 3 Certify Twisted Pair Cabling Frequency Domain Results 123 GPU71 PNG Figure 52 NEXT Plot...
Страница 162: ...Versiv Series Cabling Certification Product Family Technical Reference Handbook 126 GPU73 PNG Figure 55 ACR N Plot...
Страница 164: ...Versiv Series Cabling Certification Product Family Technical Reference Handbook 128 GPU106 PNG Figure 56 PS ACR N Plot...
Страница 167: ...Chapter 3 Certify Twisted Pair Cabling Frequency Domain Results 131 GPU75 PNG Figure 58 ACR F Plot...
Страница 179: ...Chapter 3 Certify Twisted Pair Cabling Frequency Domain Results 143 GPU92 PNG Figure 64 CMRL Plot...
Страница 182: ...Versiv Series Cabling Certification Product Family Technical Reference Handbook 146 GPU91 PNG Figure 66 CDNEXT Plot...
Страница 184: ...Versiv Series Cabling Certification Product Family Technical Reference Handbook 148 GPU78 PNG Figure 67 TCL Plot...
Страница 213: ...Chapter 5 Certify Coaxial Cabling Coaxial Autotest Results 177 GPU187 PNG Figure 81 Coaxial Impedance Results...
Страница 220: ...Versiv Series Cabling Certification Product Family Technical Reference Handbook 184...
Страница 268: ...Versiv Series Cabling Certification Product Family Technical Reference Handbook 232...
Страница 330: ...Versiv Series Cabling Certification Product Family Technical Reference Handbook 294...
Страница 338: ...Versiv Series Cabling Certification Product Family Technical Reference Handbook 302...
Страница 592: ...Versiv Series Cabling Certification Product Family Technical Reference Handbook 556...
Страница 604: ...Versiv Series Cabling Certification Product Family Technical Reference Handbook 568...
Страница 620: ...Versiv Series Cabling Certification Product Family Technical Reference Handbook 584...
Страница 669: ...Chapter 21 Specifications Display 633 GPU194 EPS Figure 213 Plug for the Headset Jack L R 3 5 mm Microphone Switch...
Страница 672: ...Versiv Series Cabling Certification Product Family Technical Reference Handbook 636...
Страница 676: ...Versiv Series Cabling Certification Product Family Technical Reference Handbook 640...
Страница 688: ...Versiv Series Cabling Certification Product Family Technical Reference Handbook 652...