![Fluke 6200-2 Скачать руководство пользователя страница 17](http://html1.mh-extra.com/html/fluke/6200-2/6200-2_user-manual_2310366017.webp)
Appliance Tester
Safe Appliance Tests
9
Safe Appliance Tests
Warning
To prevent possible electrical shock, fire, or personal injury:
•
Before you start any tests, you are strongly advised to make
reference to the Electricity at Work Regulations 1989 and any
relevant publications from the Health and Safety Executive.
•
The appliance must be switched on for all tests.
•
During tests, do not touch the appliance as some tests involve high
voltages and high currents.
•
The tests should only be performed by competent persons who are
familiar with the requirements of the type of tests suitable for
portable appliances.
•
It is potentially hazardous for both user and appliance should the
wrong type of tests be undertaken or if a test is carried out in an
incorrect sequence.
•
It is important that you fully understand the various tests required
and how they should be performed.
•
The appliance must have passed the visual inspection, the earth
bond test (Class I), and the insulation test (in this sequence) before
any other test. If any of these tests fail, further tests must be stopped
and any faults must be rectified.
•
During the load/leakage test and the touch current test, the appliance
is energized at mains voltage. For this purpose, switch on the
appliance. Appliances driven by motors or equipped with heating
units may present a danger during a test (comply with appliance
instruction manual!). Please ensure that the appliance is in a safe
condition to operate and secure before tests.
You can do tests in a single test mode or in a continuous test mode.
Single Test Mode
To do a single non-live test, push the test button and then release it.
To do a single live test (load/leakage and touch current), hold down the test button and
release it after the second beep, before you hear a third long beep.
The Tester connects the test supply, performs one test, disconnects the test supply and holds
the result on the display.
Continuous Test Mode
To start a continuous non-live test, hold down the test button for at least 2 seconds. You will
hear a long beep to indicate the Tester is in the continuous mode.
To start a continuous live test (load/leakage and touch current) hold down the test button until
you hear two beeps followed by a third beep.
The Tester connects the test supply, makes the first test and displays the first result. Then the
Tester continues to measure and display results without disconnecting the test supply. The
maximum test time is 8 minutes. After which the test terminates.