Features
The Tester can perform all the tests required for Class I and Class II appliances and conforms
to safety standard EN61010. All features for manual tests and low volume applications are
accessible from the front panel.
Front Panel Description
The connectors, controls and indicators of the Tester are shown in Table 3.
Table 3. 6200-2 Appliance Tester
SWITCH ON APPLIANCE FOR ALL TESTS
IEC
BOND 25A/200mA
TOUCH PROBE
INSULATION PROBE
CLASS II
PROBE PELV
TEST SOCKET
230V 50Hz / MAX 13A
BOND ZERO
6200-2 APPLIANCE TESTER
I
PE
< 3.5mA
(0.75mA PORTABLE
APPLIANCE)
INSULATION I SUB
BOND ZERO
IEC LEAD
EARTH BOND
LOAD / LEAK
ITOUCH
I
TOUCH
< 0.25 mA
R
ISO
> 1.0M Class I R
ISO
> 2.0M Class II
RPE < 0.1
R
ISO
> 1.0M Class I
R
PE
200mA, R
PE
25A
R
PE
< 0.1 + LEAD
PROBE ONLY WITH
CLASS II APPLIANCE
1
8
3
7
4
5
2
Euro
United Kingdom
Australia
6
hdc01.eps
No. Description
Liquid Crystal Display (LCD)
Socket to connect IEC lead for IEC Lead test
Earth connection to zero the Earth Bond test lead
Socket to connect test lead and crocodile clip for Earth Bond test
Socket to connect test probe for Insulation test, Touch Current test, Substitute Leakage test and
PELV test
Appliance Test Socket
2 USB Ports
Pushbuttons (see Table 4)