Fluidwell F190-A Скачать руководство пользователя страница 1

 
 
 
 
 

F190-A 

GENERAL PURPOSE INDICATOR WITH HIGH / LOW ALARMS 

AND ANALOG OUTPUT 

 
 
 

 
 
 

Signal input sensor: (0)4-20mA 
Signal outputs: (0)4-20mA/ 0-10V ref. the value or percentage 
Alarm outputs: maximum four alarm outputs 
Options: Intrinsically Safe, Modbus communication, backlight 

 

 

F-Series - Field mounted indicators for safe and hazardous areas.  

More info: www.fluidwell.com/fseries

 

Содержание F190-A

Страница 1: ...input sensor 0 4 20mA Signal outputs 0 4 20mA 0 10V ref the value or percentage Alarm outputs maximum four alarm outputs Options Intrinsically Safe Modbus communication backlight F Series Field mount...

Страница 2: ...to the general waste system or into a landfill At the end of its life equipment shall be disposed of according to the local regulations regarding waste of the electrical and the electronic equipment P...

Страница 3: ...e F190 A or connected instruments A caution indicates actions or procedures which if not performed correctly may lead to personal injury or incorrect functioning of the F190 A or connected instruments...

Страница 4: ...P menu 6 Analog output 17 3 2 9 Explanation of SETUP menu 7 Relay output 19 3 2 10 Explanation of SETUP menu 8 Communication 19 3 2 11 Explanation of SETUP menu 9 Others 19 4 Installation 20 4 1 Gener...

Страница 5: ...FW_F190A_v1702_02_EN docx Page 5 Appendix A Technical specification 41 Appendix B Problem solving 44 Appendix C Communication variables 45 Index of this manual 48 Declaration of Conformity 49...

Страница 6: ...ounting possibilities with aluminum or GRP enclosures for harsh industrial surroundings ability to process all types of signals transmitting possibilities with analog alarm and communication option ou...

Страница 7: ...f power break down or empty battery To extend the battery life time option please make use of the power management functions as described in chapter 3 2 3 Display information The unit has a large LCD...

Страница 8: ...access to the SETUP menu please read chapter 3 This key is used to SELECT other display information or to increase a value The arrow key is used to configure the unit please read chapter 3 This key i...

Страница 9: ...its and to change the blinking digit 3 set the new alarm value by pressing the PROG ENTER key When data is altered but PROG ENTER has not been pressed yet then the alteration can still be cancelled by...

Страница 10: ...observed Ensure that the measuring system is correctly wired up according to the wiring diagrams The housing may only be opened by trained personnel Take careful notice of the Safety rules instructio...

Страница 11: ...s a unique number which is displayed below the word SETUP at the bottom of the display The number is a combination of two figures The first figure indicates the function group and the second figure th...

Страница 12: ...ing When data is altered but ENTER is not pressed then the alteration can still be cancelled by waiting for 20 seconds or by pressing ENTER for three seconds the PROG procedure will be left automatica...

Страница 13: ...W LOW 0 0 999 9 seconds 2 6 DELAY ALARM LOW 0 0 999 9 seconds 2 9 DELAY ALARM HIGH 0 0 999 9 seconds 2 A DELAY ALARM HIGH HIGH 0 0 999 9 seconds 3 DISPLAY 3 1 ALARM SET operator setup hidden disable 3...

Страница 14: ...racters with setup 1 3 xxx means customized time unit with a slash and three characters see setup 1 3 To enable xxx it is required to select custom with setup 1 1 CUSTOM 1 3 An own value can be select...

Страница 15: ...lue is higher as this value ALARM HIGH HIGH 2 6 The high high alarm is set with this setting An alarm will be generated as long as the value is higher as this value DELAY TIME ALARM LOW LOW 2 7 An ala...

Страница 16: ...UP MENU 5 SENSOR FORMULA 5 1 The F190 A can process the 0 4 20mA signal in two ways Interpolation or Square root Interpolation the signal is processed linear R S x I Square root for differential press...

Страница 17: ...ting it is possible to calibrate the input value for 20mA as the signal from the sensor might not be exact 20 0 mA at maximum signal This function will measure the real output value at maximum signal...

Страница 18: ...t the analog signal is not being used for any application After pressing PROG the current will be about 20mA The current can be increased decreased with the arrow keys and is directly active Press ENT...

Страница 19: ...all and manage the appropriate safety measures to protect the network the product and the communication against any kind of security breaches The functions described below deal with hardware that is n...

Страница 20: ...when the housing cover is removed or the panel cabinet has been opened danger from electrical shock The housing may only be opened by trained persons authorized by the operator of the facility Take c...

Страница 21: ...30mm 30mm M20 x 1 5 M16 x 1 5 M16 x 1 5 30mm 30mm M20 x 1 5 M20 x 1 5 M20 x 1 5 25mm 25mm 1 2 NPT 0 9 3x 1 2 NPT 0 12 0 12 HA HM HN HO HP HT HU 6 x M12 12mm 12mm 24mm 24mm 36mm 36mm 14mm 17mm 115 mm...

Страница 22: ...36 120 mm 4 72 HD HK HK back box flat bottom HE HF HG HH D 12mm 12mm 12mm 24mm 24mm 36mm 36mm 14mm 17mm 22 5mm 30mm 30mm D 16mm D 20mm 0 9 D 22mm 0 866 22 5mm 25mm 25mm D 20mm D 20mm D 16mm HC 75 mm...

Страница 23: ...that came with a power module type PM 110V 230V AC or type PD PF with an option OR the relays can handle 110V 230V AC shall be connected to the Protective Earth PE stud which is installed in the metal...

Страница 24: ...ies sensor PLC etc Inside the Fluidwell display the common grounds are internally connected to each other The PE connection The PE connection is made with the PE stud inside the back panel and the 4 m...

Страница 25: ...one of the mounting screws that attaches the front panel to the panel Type PM 110 230V AC The PE connection to the metal cover is made with the serrated washers and the mounting screws The PE connect...

Страница 26: ...STIC GRP ENCLOSURE The PE connection The F190 A in a GRP enclosure meets the requirements of class 2 double insulated Therefore the incoming PE wire is terminated with an insulating end cap Type PM 11...

Страница 27: ...al connectors Standard configuration and options 4 4 6 SENSOR SUPPLY For type PB PC PX AP There is no real sensor supply out available Only a limited power supply is available This power supply MAY NO...

Страница 28: ...typical Sensor Vout selection Sensor supply out A 1 2 3 4 NOTE Use an AC autotransformer spartrafo with galvanic isolation int off off Not suitable for analog sensors 3V DC 1mA ext on on off on off o...

Страница 29: ...type PD PF PM or PX min 24V DC Fig 9 Terminal connections Active output typical Type OR Two mechanical relay outputs are available with this option Max switch power 240V 0 5A per output Requires powe...

Страница 30: ...5mA signal will be generated on these terminals Max driving capacity 1000 Ohm 24VDC Requires power supply type PD PF PM PX Fig 12 Terminal connections 4 20mA analog output typical Type AB An active 0...

Страница 31: ...Active 0 10V analog output typical Terminal 09 11 Type A Sensor input general The F190 A requires a 0 4 20mA sensor signal which will be processed 4 times a second with a 16 bits accuracy The input is...

Страница 32: ...terminal connectors Standard configuration and options Full serial communications and computer control in accordance with RS232 length of cable max 15 meters or RS485 length of cable max 1200 meters...

Страница 33: ...st IP65 in accordance with IEC 60529 suitable cable entries and blanking elements must be used and correctly installed For enclosures and windows with a high surface resistance potential charging haza...

Страница 34: ...er and year of production This information can be looked up in the setup menu Others Fig 21 Example serial number typical Label information F1xx XI inside and outside the enclosure Fig 22 Label inform...

Страница 35: ...it supply connected to terminals 7 and 8 type AP The maximum values for any of those circuits are those as defined for group IIB IIIC No other active external intrinsically safe circuits may be connec...

Страница 36: ...ower supply is connected The sensor supply voltage is fixed 8 2V DC Set the sensor supply 1 Make the F190 A safe If applicable mind the battery power 2 Open the F190 A and carefully remove the cable c...

Страница 37: ...FW_F190A_v1702_02_EN docx Page 37 5 3 CONFIGURATION EXAMPLES INTRINSICALLY SAFE APPLICATIONS Fig 26 Configuration example Intrinsically safe...

Страница 38: ...FW_F190A_v1702_02_EN docx Page 38 Fig 27 Configuration example Intrinsically safe...

Страница 39: ...ry with the utmost care to prevent a short circuit and damage 4 Do not recharge crush disassemble incinerate heat above its rated temperature or expose the contents to water 5 Dispose of the battery i...

Страница 40: ...that the function is disabled if not in use or else it will have a major influence on the battery life time Display update fast display update uses significantly more power Pulse output and communicat...

Страница 41: ...IP65 TYPE 4 X Drilling 2x PG9 1x M20 Drilling 2x M16 1x M20 Drilling 1x M20 Drilling 2x M20 Drilling 6x M12 Drilling 1x NPT Drilling 3x NPT No drilling No drilling Drilling 2x 16mm 0 63 1x 20mm 0 78 D...

Страница 42: ...r percentage Accuracy 10 bit Error 0 05 update 8 times a second Software function to calibrate the 4 00mA and 20 00mA levels precisely within set up Load max 1 kOhm Type AA Active 4 20mA output requir...

Страница 43: ...NM3 mg g Kg TON GAL USGAL IGAL lb bbL cf scf p rev C F K M mm CM mtr inch Ft Yd PSI psig mbar bar barg bara KPA KPAG INHG mmHg MH2O INH2O Ph mV mA uS PPM RPM no unit custom up to 8 characters Time uni...

Страница 44: ...lue selected process value or percentage SETUP 2 3 2 6 are the correct alarm values programmed SETUP 2 7 2 A are the correct alarm delay times programmed The password is unknown If the password is not...

Страница 45: ...cess Value 2 R int32 signed 999999 999999 Representation unit decimals depending on variables 30 32 d 44 h 0x02C 40045 percentage 1 R uint16 0 0 100 0 d 516 h 0x204 40517 error status bitfield 1 R uin...

Страница 46: ...r w uint32 0 1 Sign for alarm value high variable 243 d 237 h 0x0ED 40238 alarm value high high 2 r w uint32 0 9999999 Representation 9999 999 9999999 depending on variable 69 and 253 d 253 h 0x0FD 40...

Страница 47: ...ISTERS R W TYPE VALUE REMARKS d 135 h 0x087 40136 relay 1 1 r w uint16 0 off 1 LL 2 LO 3 HI 4 HH 5 all d 136 h 0x088 40137 relay 2 1 r w uint16 0 off 1 LL 2 LO 3 HI 4 HH 5 all d 137 h 0x089 40138 rela...

Страница 48: ...10 Dimension enclosures 21 display update 16 flowmeter 16 high alarm output 29 32 Installation 20 Intrinsic safety 33 35 Intrinsically Safe options 36 IP classification 20 keys 8 Low battery alarm 9...

Страница 49: ...FW_F190A_v1702_02_EN docx Page 49 DECLARATION OF CONFORMITY...

Страница 50: ...low 0 0 sec 2 8 delay alarm low 0 0 sec 2 9 delay alarm high 0 0 sec 2 A delay alarm high high 0 0 sec 3 DISPLAY 3 1 alarm set operator 3 2 function value 3 3 light 100 3 4 backlight alarm off 4 POWER...

Страница 51: ...ELAYS 7 1 relay 1 off 7 2 relay 2 off 7 3 relay 3 off 7 4 relay 4 off 8 COMMUNICATION 8 1 speed 9600 8 2 address 1 8 3 mode BUS RTU 8 4 databits 8 bits 8 5 parity none 9 OTHERS 9 1 model F190 A F190 A...

Страница 52: ...dwell bv PO box 6 Voltaweg 23 Website www fluidwell com 5460 AA Veghel 5466 AZ Veghel Find your nearest representative www fluidwell com representatives The Netherlands The Netherlands Copyright Fluid...

Отзывы: