FW-F010-P-M_v0404_01_EN.docx
4.6.2
TERMINAL 4-5: POWER SUPPLY - TYPE PX (DEFAULT) AND PD (OPTION)
To power the F010-P an internal battery can be used (type PB) and / or an external DC power
supply of 8-30V DC (type PX) or 16-30V DC (type PD).
Connect the "
-
" to terminal 4 and the "
+
" to terminal 5.
When power is applied to these terminals, the optional internal battery will be disabled / enabled
automatically to extend the battery life time.
4.6.3
TERMINAL 6: POWER SUPPLY TYPE PD: 8.2V SENSOR SUPPLY
With this option, a limited power supply for the sensor is available, for example to power a Namur
sensor. It offers 8.2V DC (max. 5mA).
This terminal is only available if type PD has been ordered
4.6.4
TERMINAL 9-10: POWER SUPPLY BACKLIGHT - TYPE ZB (OPTION)
To power the backlight, a voltage in the range 20-30V DC has to be connected.
Maximum current 30mA. Connect the "
-
" to terminal 9 and the "
+
" to terminal 10.
Fig. 21: Terminal connections - Backlight (ZB).