DATA LOGGING (TYPE ZL)
Type ZL
Powerful data and event logging functions and logbooks are available.
Log records go round trip, the oldest entries are overwritten when the logbook is full.
Note
When ordered with type ZL – Datalogging, standard basic day totals are not available.
Interval log
1000 records
Daily log
1000 records
Single daily log: 1000 days, 1 record per day
Dual daily log: 500 days, 2 records per day
Event log
500 records
A.5
DIRECTIVES/STANDARDS AND HAZARDOUS AREA CLASSIFICATION
APPLICABLE DIRECTIVES AND STANDARDS
EU Directives
See
Section E: Legal information [»70]
EMC
FCC 47 CFR part 15
CSA
CSA 22.2 No. 25, CSA 22.2 No. 30, CAN/CSA 22.2 No. 94-M91, CSA C22.2 No. 61010-1-12
FM
FM3600; FM3615; FM3616; FM3810
IP & TYPE
EN 60529; NEMA 250
HAZARDOUS AREA CLASSIFICATION
ATEX
Gas:
II 2 G Ex d IIC T6 Gb.
Dust:
II 2 D Ex tb IIIC T85°C Db.
IECEx
Gas: Ex d IIC T6 Gb.
Dust: Ex tb IIIC T85°C Db.
CSA c-us
Class I, Division 1, Grps A, B, C, D
Class II/III, Division 1, Grps E, F, G
Class I, Zone 1, Aex d IIC T6/T5 Gb
Zone 21, Aex tb IIIC T85°C/T100°C Db
FM
Class I, Division 1, Grps A, B, C, D
Class II/III, Division 1, Grps E, F, G
Class I, Zone 1, Aex d IIC T6/T5 Gb
Zone 21, Aex tb IIIC T85°C/T100°C Db