TECHNICAL SPECIFICATION
General
Display
Type
High intensity numeric and alphanumeric LCD, UV-resistant, with bright backlight.
When only battery or loop powered, the backlight is not operational.
Dimensions
54 x 29mm (2.13” x 1.14”).
Digits
Seven 12mm (0.47
”
) and eleven 7mm (0.28
”
) digits. Various symbols and measuring units.
Refresh rate
During operation 8 times/sec, switches to 1 time/sec after 30 sec without operation.
Enclosures
Material
GRP, UV-resistant and flame retardant.
Sealing
EPDM gasket.
Control keys
Two industrial micro-switch keys. UV-resistant Polyester keypad.
Rating
IP65, NEMA Type 4X
Dimensions
92 x 92 x 60mm (3.62” x 3.62” x 2.36”)
- W x H x D.
Weight
200 gram / 0.44 lbs.
Cable entries
Knock-out type.
Side: 2x 16mm/0.63”
Bottom: 1x
20mm/0.79”
Note: the rear-enclosure can be rotated in steps of 90°.
Operating temperature
Ambient
-20°C to +60°C (-4°F to +140°F).
Power requirements
External power supply
10 - 30V DC. Max consumption: 25mA.
The power supply will also supply the backlight and the 8.2V DC sensor supply.
Battery
Primary, non-rechargeable, Lithium metal Thionyl Chloride (Li/SOCl2), 1x3.6V/2.4Ah, AA size
(IEC-R6, ANSI size15).
Life-time depends upon settings and configuration - up to approx. 2 years.
Battery replacement: only with identical specification!
Loop powered
Loop powered, analog output. 12 - 30V DC.
Sensor excitation
Standard
Terminal 3: 3V DC reference voltage for pulse signals, 1.2V DC for coil pick-up. Max.
100μA.
This is not a real sensor supply. Only suitable for sensors with a very low power consumption
like coils (sine wave) and reed-switches.
With external power supply Terminal 4 : 8.2V DC, max. 10mA.
Terminal connections
Type
Fixed terminal strip. Wire max. 1.5 mm
2
.
Data protection
Type
FRAM backup of all settings.
Backup of running totals every minute. Data retention at least 10 years.
Password
Configuration settings can be password protected.
Directives and Standards
EMC
EN 61000-6-2
BS 61000-6-2
EN 61000-6-3
BS 61000-6-3
EN 61326-1
BS 61326-1
FCC 47 CFR part 15
RoHS
EN 50581
BS EN 50581
EN IEC 63000
BS EN IEC 63000
IP & TYPE
EN 60529
NEMA 250